Transformers and Motors
Transformers, Motors and Generators
BeginnerLesson 5 of 7 in Electrical Principles for Technicians Course
What you will learn
- Explain how a transformer uses mutual induction to change an AC voltage, calculate voltages, currents and turns with the turns ratio, and judge the losses, efficiency, ratings and types of single- and three-phase transformers.
- Explain how a transformer changes an AC voltageDescribe the windings and core of a transformer and explain step by step how mutual induction carries energy from the primary to the secondary winding, and why a transformer needs AC.
- Calculate voltages, currents and turns with the turns ratioUse the voltage and current ratios of an ideal transformer to find secondary voltages, numbers of turns and primary and secondary currents, and check each answer with the power balance and the VA rating.
- Judge transformer losses, efficiency, ratings and typesSeparate iron and copper losses, calculate efficiency at different loads, read the rating plate of single- and three-phase transformers and choose between isolating, safety, control and autotransformers.
- Explain how a transformer changes an AC voltage
- Apply electromagnetic induction to explain how rotating machines generate AC and DC, calculate induced voltage and frequency, and describe how alternators are built, controlled and used.
- Explain how a moving conductor or rotating coil generates voltageUse the generator rule, the induced-EMF formula and the frequency formula to explain and calculate the output of a rotating coil, and explain how slip rings and a commutator give AC or DC.
- Describe alternators and how their output is controlledExplain how three-phase alternators are built, how speed sets the frequency and excitation sets the voltage, and how generating sets, grid generators and vehicle alternators supply their loads safely.
- Explain how a moving conductor or rotating coil generates voltage
- Use the force on a current-carrying conductor to explain DC motor operation, calculate force, torque, back EMF and starting current, and compare brushed DC motors with brushless DC, stepper and servo motors.
- Explain the motor principle, commutation and back EMFExplain how the force on a current-carrying conductor turns an armature, why a commutator is needed, and how back EMF limits the running current; calculate force, torque, back EMF and starting current.
- Compare DC motor types and electronically commutated motorsCompare permanent-magnet, shunt, series and compound DC motors, and recognize brushless DC, stepper and servo motors by their construction, behavior, uses and connection needs.
- Explain the motor principle, commutation and back EMF
- Explain how a rotating field drives an induction motor, calculate speed, slip, current, power and torque, choose between direct, star–delta and soft starting, and explain and connect single-phase motors.
- Explain the rotating field, synchronous speed and slipExplain how three-phase currents produce a rotating field that drags a cage rotor round, calculate synchronous speed and slip, and relate induction motors to synchronous and traction motors.
- Calculate the power, current and torque of a three-phase motorFollow the power flow of a three-phase motor, calculate its rated current and torque from nameplate data, and explain how current, power factor and efficiency change with load and voltage.
- Choose a starting method: direct, star–delta or soft startExplain why large motors need reduced starting current, calculate the effect of star–delta (wye–delta) starting, describe the starter circuit and its overload setting, and compare it with direct-on-line and soft starting.
- Explain and connect single-phase motorsExplain why a single-phase motor needs a starting arrangement, compare split-phase, capacitor, shaded-pole and universal motors, reverse and test them, and run a small three-phase motor on a single-phase supply.
- Explain the rotating field, synchronous speed and slip
- Interpret IEC and NEMA motor nameplates, choose the star or delta connection and direction of rotation for the supply, and select, set and check motor protection with insulation, resistance, current and power-factor measurements.
- Read an IEC or NEMA motor nameplateDecode every field of a motor nameplate, check that its values are consistent, and use them to find the connection, current, poles, slip, torque and operating limits for a given supply.
- Connect a three-phase motor in star or delta and set its directionChoose star or delta from the nameplate and the supply voltage, place the links on the terminal board, connect NEMA nine-lead motors, and check and change the direction of rotation.
- Protect a motor and check it with measurementsChoose short-circuit and overload protection, set an overload relay from the nameplate, and check a motor with insulation resistance, winding resistance, starting current and power factor measurements.
- Read an IEC or NEMA motor nameplate
Transformers and Motors study guide
1Explain and calculate transformers
A transformer changes an AC voltage without a moving shaft. The same magnetic link explains its voltage ratio, why current rises when a load is connected, and why it still uses energy at no load. Work from the windings to the calculations, then use losses and rating-plate data to judge what a real transformer can supply. The distinction between winding values and line values becomes essential when three phases share one core.
1.1 Explain how a transformer changes an AC voltage
A transformer transfers energy between AC circuits through a shared magnetic field. Its primary winding connects to the supply; its secondary winding connects to the load. A laminated iron core guides the flux through both windings. Most transformers have separate windings, so the magnetic link transfers energy without a conductive connection between the circuits.
Follow one AC cycle
An AC voltage applied to the primary produces a small magnetizing current. This sets up alternating flux in the closed core. The changing flux induces an electromotive force, or EMF, in every linked turn of both windings. When a load completes the secondary circuit, that EMF drives secondary current. Each turn links nearly the same flux, so twice as many turns gives twice the induced voltage.
With the secondary open, the primary still takes a small no-load current to magnetize the core and supply its losses. Connecting a load makes secondary current flow. Its magnetic effect opposes the original flux change, and the primary takes extra current to maintain the flux required by the supply. The load therefore determines most of the input current.
Why the core has thin layers
Alternating flux also induces circulating currents in the iron. Thin steel sheets, insulated from one another, interrupt these eddy currents and reduce heating. The closed core needs little magnetizing current. Opening its magnetic path makes that current rise and weakens the secondary output.
The low-voltage winding has fewer turns but carries more current, so it uses thicker wire and generally has lower resistance. At switch-on, the core can also cause a brief inrush current much larger than normal current. Primary protection must tolerate this short event while still clearing faults.
Connect voltage with flux
For a sinusoidal supply, the rms induced voltage is
Here frequency is in hertz, turns are counted by , and peak flux is in webers. With 920 turns on 230 V at 50 Hz, calculate the denominator first: . Then
A 10 cm² core has an area of 0.001 m², so its peak flux density is about 1.13 T. Keep the area conversion in the calculation: using 10 as the area in square meters would give the wrong flux density.
Why supply frequency matters
At fixed voltage and turns, flux rises when frequency falls. A 60 Hz transformer supplied at 50 Hz has times its design flux. That 20% increase can saturate the core and cause overheating. A 50 Hz transformer at the same voltage on 60 Hz has less flux; the rated frequency still belongs in the suitability check.
Steady DC produces no continuing flux change after switch-on. The secondary then has no sustained induced voltage, while the primary current is limited mainly by its low winding resistance. A battery therefore cannot feed an ordinary transformer directly to obtain a lower DC voltage; that job needs an electronic converter.
Key Takeaways
- Changing core flux induces EMF in both windings.
- Load current on the secondary causes extra primary current.
- Laminations reduce eddy-current heating.
- At fixed voltage, lower frequency means higher peak flux.
- Steady DC can overheat an ordinary transformer.
1.2 Calculate voltages, currents and turns with the turns ratio
The number of turns sets the voltage change. Current changes in the opposite direction, because an ideal transformer transfers the same power through both sides. Label the supply side 1 and the load side 2 before choosing a ratio.
Use the voltage ratio
For an ideal transformer,
A step-down transformer has fewer secondary turns; a step-up transformer has more. To find an unknown, rearrange the equation first. For secondary turns, use
A 230/12 V transformer with 920 primary turns needs secondary turns. The lower voltage belongs to the winding with fewer turns. Reversing the voltage fraction would predict thousands of secondary turns for a step-down transformer, which fails that check.
Find current from the load
A 60 W resistive lamp supplied at 12 V draws . Ignoring losses, the primary supplies the same 60 W, so . The current ratio is
The high-voltage side carries the smaller current. Multiplying 5 A by the voltage reduction factor would predict a huge primary current and far more input power than output power.
For a step-up example, 400 primary turns and 1,600 secondary turns give a factor of four. A 230 V primary therefore gives 920 V at the secondary. Supplying 0.5 A at 920 V takes about 2 A at 230 V: both sides carry 460 VA. A higher output voltage does not mean free extra power.
Respect the VA limit
A transformer is rated in volt-amperes, because winding heating depends on current and the magnetic design depends on voltage and frequency. The load's power factor changes its useful watts without removing those limits. For single-phase operation, apparent power is .
A 100 VA, 400/24 V control transformer can supply
Its ideal primary current at that load is . Several control coils share the same capacity: add their VA demands before comparing the total with 100 VA. A 100 VA rating is not a guarantee of 100 W for every load.
Check a real measurement
Real windings have resistance, and some flux fails to link both windings. Their voltage drops become larger as load current rises. A lightly loaded 24 V control secondary may measure 26 V and fall toward its rated value under load. Compare the reading with the load condition and rating, rather than diagnosing a winding fault from the unloaded reading alone.
Key Takeaways
- Voltage follows the turns ratio; current follows its inverse.
- Check the result by comparing the VA on both sides.
- All connected loads share the transformer VA capacity.
- Secondary voltage commonly falls as load current rises.
1.3 Judge transformer losses, efficiency, ratings and types
A real transformer heats up even though its shaft never turns. Separate the losses that continue whenever it is energized from those that grow with load, then use the plate to check its current, fault level and construction.
Calculate losses at the actual load
Iron losses come from hysteresis and eddy currents. At the same voltage and frequency they stay nearly constant. Copper losses are winding heating and follow current squared. At half rated current, they are one quarter of their full-load value.
For a 10 kVA transformer with 120 W iron loss and 250 W full-load copper loss, a unity-power-factor full load gives
At half load, output is 5,000 W and copper loss is . Efficiency is . At 10% load, only 2.5 W of copper loss remains, but the 120 W iron loss still lowers efficiency to about 89.1%. Maximum efficiency occurs when copper loss equals iron loss: here the load fraction is . An energized, unloaded transformer still consumes energy.
Read three-phase values correctly
The plate gives kVA, voltages, currents, frequency and phases. Large transformers also show cooling, insulation, short-circuit voltage and vector group. The stated three-phase voltages are line-to-line values. For 630 kVA at 400 V,
The 10 kV side carries about 36.4 A. A short-circuit voltage of 4% means 4% of rated primary voltage drives rated current with the secondary shorted. The transformer-limited fault estimate is . Supply impedance reduces this estimate; protective-device breaking capacity must suit the prospective fault current.
In Dyn11, the high-voltage winding is delta, the low-voltage winding is star, and its neutral is accessible. The low-voltage phasor leads by 30°. A 10 kV/400 V Dyn11 unit has 10,000 V per primary winding but only per secondary winding. Its winding ratio is about 43.3, although its line-voltage ratio is 25.
Choose the transformer type
| Type | Construction and job |
|---|---|
| Isolating | Separate windings with double or reinforced insulation separate an output circuit from the supply. |
| Safety isolating | Provides extra-low voltage, at most 50 V AC including no load. |
| Control | Supplies control loads such as contactor coils. |
| Autotransformer | One tapped winding changes voltage without electrical isolation. |
| Current transformer | Reduces a large primary current to a standard measuring current, often 5 A. |
A current transformer's secondary must stay closed while primary current flows. Short its secondary before disconnecting a meter: an open secondary can develop dangerous voltage and overheat the core.
Key Takeaways
- Iron loss is nearly constant; copper loss follows current squared.
- Efficiency uses real output watts and all losses.
- Three-phase plate voltages are line-to-line values.
- Vector groups identify winding connections and phase displacement.
- An autotransformer provides no electrical isolation.
- Never open a current-transformer secondary carrying primary current.
2Explain how generators and alternators produce electricity
Mechanical motion can drive charge through a circuit when a conductor cuts a magnetic field. Follow that energy transfer from one moving conductor to a three-phase alternator, then separate the jobs of the speed governor and voltage regulator. A generator supplying its own load behaves differently from one locked to a large grid, so the operating situation matters when predicting changes in voltage, frequency and power.
2.1 Explain how a moving conductor or rotating coil generates voltage
A generator converts mechanical input into electrical output. A magnetic field, a conductor and motion that cuts the field are needed. The conductor can move through a stationary field, or the field can move past a stationary conductor.
Generate voltage in one conductor
For active length perpendicular to a uniform field and motion perpendicular to both,
Use tesla, meters and meters per second. A 0.25 m conductor moving at 10 m/s in a 0.8 T field gives . Several active conductors connected in series add their voltages. Motion along the field lines produces no EMF because the conductor cuts no flux.
Fleming's right-hand rule gives the induced-current direction. Hold thumb and first two fingers mutually perpendicular: first finger points from north to south, thumb gives motion, and second finger gives conventional current. Lenz's law explains the reaction: current in a loaded generator produces a force opposing the driving motion. More electrical load therefore requires more mechanical torque.
Follow a rotating coil
A coil rotating steadily in a uniform field generates a sinusoidal voltage. Its EMF is greatest when its sides cut the field at right angles; the coil's plane then lies along the field. A quarter turn later the sides move along the field and the instantaneous EMF is zero. In a two-pole machine, one revolution gives one electrical cycle.
Keep voltage and flux change distinct. Maximum linked flux occurs where the rate of change is zero, so maximum flux and maximum induced EMF do not occur at the same coil position. For a particular rotating machine, : stronger flux, more speed or more series turns raises generated voltage.
Take AC or DC from the coil
Slip rings keep each coil end connected to the same external terminal. The coil voltage reverses every half turn, so the output is AC. A split commutator swaps the external connections every half turn. The coil still generates alternating EMF internally, but the terminal polarity stays the same. One coil gives pulsating DC; many coils and segments smooth the output.
Count pole pairs
Alternator frequency is
where is pole pairs and speed is in rpm. Four poles means two pairs. At 1,500 rpm the frequency is 50 Hz; at 1,800 rpm it is 60 Hz. A 150 rpm hydro generator needs pairs, or 40 poles, for 50 Hz. Using the number of poles in the pole-pair formula doubles the answer.
The same machine can reverse its energy flow. During regenerative braking, a driven motor sends electrical energy back to a battery or supply. Permanent-magnet machines retain their field after the supply is removed, so a turning shaft can still generate terminal voltage. Bring the shaft to rest before treating a disconnected machine as electrically inactive.
Key Takeaways
- A conductor must cut magnetic flux to generate EMF.
- A loaded generator resists the motion driving it.
- Slip rings deliver AC; a commutator delivers one-polarity output.
- In the frequency formula, count pole pairs.
- A driven motor can return energy as a generator.
2.2 Describe alternators and how their output is controlled
Practical alternators usually put the magnetic field on the rotor and the power windings on the stator. This lets large output currents leave through fixed terminals. The rotor field comes from permanent magnets or DC excitation; a brushless exciter supplies a wound rotor through rotating diodes without brushes.
Keep frequency and voltage separate
Three stator windings spaced 120 electrical degrees apart generate equal voltages displaced by one third of a cycle. Their order is the phase sequence. On an independent generating set, an engine governor holds speed and an automatic voltage regulator, or AVR, adjusts excitation.
A four-pole set needs 1,500 rpm for 50 Hz. If a load slows it to 1,440 rpm, frequency becomes . Raising excitation cannot restore 50 Hz; the engine must recover its speed. If speed stays correct but voltage falls, the AVR increases field current. Inductive loads tend to produce more voltage drop than resistive loads.
Adding electrical load also demands more mechanical power. The engine must provide more torque, using more fuel. Voltage regulation cannot provide energy that the prime mover fails to supply.
Connect to an existing supply
A synchronous generator connected to a large grid is held at the speed set by grid frequency and its poles. Increasing its mechanical input increases real power delivered to the grid. Changing excitation mainly changes reactive power exchange.
Before paralleling, check equal voltage, equal frequency and the same phase sequence. The voltages must also be in phase when the breaker closes. Equal frequency alone allows a fixed phase-angle difference, so it does not complete synchronization.
A portable generator supplies a building through a proper transfer switch. Direct backfeeding can energize the distribution network and expose line workers to voltage from the building.
Recognize other generators
A conventional vehicle alternator has a claw-pole rotor, field brushes and slip rings, and a three-phase stator. Six diodes form a bridge rectifier that delivers DC to the battery. A field regulator commonly holds a conventional 12 V system near 14 V, often 13.5–14.5 V. Smart charging systems vary their commanded voltage, so diagnosis compares voltage and charging current with the vehicle's operating state and service data. A single reading near 12.6 V needs that context.
A self-excited DC generator uses residual magnetism to start building voltage. If that magnetism is lost, it may need controlled external field excitation to restore it. Alternators with rectifiers have largely replaced these DC generators in vehicle charging.
An induction machine driven above synchronous speed can feed real power back into a connected supply. Its slip is then negative: a four-pole machine driven above 1,500 rpm on 50 Hz is in its generating region. The supply provides the magnetic excitation needed for this grid-connected operation.
Key Takeaways
- On an independent set, speed controls frequency and excitation controls voltage.
- A grid-connected synchronous generator stays at grid-set speed.
- Synchronization needs matching voltage, frequency, sequence and phase angle.
- A vehicle alternator rectifies three-phase AC to DC.
- Above synchronous speed, a grid-connected induction machine can generate.
3Explain how DC motors work and compare their types
A DC motor turns electrical input into shaft torque, but its turning armature also generates a voltage. That back EMF explains both the modest running current and the very large current at standstill. Use this link to understand starting, load changes and reversing, then compare the field arrangements of brushed motors with the controllers and feedback used by brushless, stepper and servo systems.
3.1 Explain the motor principle, commutation and back EMF
A current-carrying conductor in a magnetic field experiences a force. In a motor coil, the forces on opposite sides form a turning moment, or torque. The motor also generates a voltage as it turns, and that voltage is central to understanding its current.
Turn force into torque
For a conductor at right angles to a uniform field,
With 0.5 T, 20 A and 0.3 m active length, the force is 3 N. Fleming's left-hand rule gives its direction: first finger for field, second finger for conventional current, thumb for force. The right hand is used for generation.
For two active coil sides at radius 0.05 m, each with 3 N tangential force, torque is per turn. Whole-motor torque follows . More armature current gives more torque at the same flux.
A commutator reverses coil current as each coil passes the neutral position, keeping torque in one direction. Many coils give smoother torque. Brushes need enough length and spring pressure to maintain contact; a burned or grooved commutator and heavy sparking indicate a maintenance problem.
Account for back EMF
The rotating armature cuts flux and produces back EMF that opposes the supply:
At 220 V, 25 A and 0.4 Ω armature resistance, the resistance drop is , leaving . Electrical input is 5,500 W. The armature converts to mechanical form, and heats the winding. Mechanical and iron losses reduce the final shaft output further.
Limit starting current
At standstill, back EMF is zero. Applying 220 V directly to 0.4 Ω would give . To limit this to 50 A, total resistance must be . The armature already provides 0.4 Ω, so add 4.0 Ω. As speed and back EMF rise, remove the added resistance in steps. An electronic controller can instead raise voltage gradually.
A load increase slows the motor slightly. Back EMF falls, the difference between supply and back EMF grows, and armature current rises. The extra current produces the extra torque. A stall removes back EMF altogether and causes rapid heating.
Change speed or direction
Speed follows the ratio of back EMF to flux. More armature voltage raises speed; weakening the field also raises speed but reduces torque available per ampere. To reverse a wound-field motor, reverse the armature or the field connections. Reversing both preserves torque direction. In a permanent-magnet motor the field is fixed, so reversing its supply polarity reverses rotation.
Key Takeaways
- The left-hand rule gives motor-force direction.
- Commutation keeps coil torque acting in one direction.
- Back EMF opposes the supply and limits running current.
- Starting resistance is the required total minus armature resistance.
- Reverse either armature current or field direction to reverse a wound-field motor.
3.2 Compare DC motor types and electronically commutated motors
The field source and the way current is switched determine a DC motor's behavior. Identify those features before predicting starting torque, speed changes or the connection it needs.
Compare brushed field arrangements
| Type | Field and behavior | Typical use |
|---|---|---|
| Permanent-magnet | Fixed magnetic field; speed follows voltage and torque follows current. | Wipers, windows and small pumps. |
| Shunt | Field in parallel with armature; speed changes little with load. | Machines needing nearly steady speed. |
| Series | Field carries armature current; high starting torque and strong speed change with load. | Starters, hoists and traction. |
| Compound | Series and shunt fields combine strong starting torque with controlled no-load speed. | Presses and conveyors. |
A series motor can overspeed when its load disappears. Keep its mechanical load connected; a belt that can come off is unsuitable as its sole load connection. Losing a shunt field can also cause dangerous overspeed. Its protection must remove armature power if the field fails; never arrange an independent field switch that leaves the armature energized after field loss.
IEC markings identify the armature as A1–A2, series field as D1–D2, shunt field as E1–E2 and separately excited field as F1–F2. A series field has thick wire and very low resistance; a shunt field has many thinner turns and higher resistance.
Move commutation into electronics
A brushless DC, or BLDC/EC, motor has a permanent-magnet rotor. A controller switches the stator windings in sequence using Hall sensors or winding back EMF to determine rotor position. Removing brushes reduces maintenance. Fans, pumps and e-bikes commonly use this arrangement. The motor needs its matching controller; plain DC across the bare motor windings does not create the required switching sequence.
Count steps or measure position
A stepper advances through fixed angles as its driver changes the winding pattern. At 1.8° per full step, steps make a revolution. Fifty steps turn 90°. At 1,000 steps per second, the shaft turns five revolutions per second, or 300 rpm. An open-loop controller counts commands, so excessive load or acceleration can cause missed steps and lost position.
A servo system measures actual position or speed with an encoder or resolver. Its drive compares this feedback with the command and corrects the difference. This closed loop lets a robot axis hold its commanded position as load changes. The motor is often a permanent-magnet synchronous or brushless type; the feedback and control make the system a servo.
For BLDC, stepper and servo systems, connect motor power leads to the specified controller or drive. Keep feedback and power cabling arranged and shielded as the manufacturer requires. Use the motor's data to select and configure the drive; set direction by the specified command or lead arrangement.
Key Takeaways
- Series motors need their load to limit speed.
- Shunt-field loss needs protection that removes armature power.
- BLDC motors use electronic commutation.
- Open-loop steppers count commanded steps; a servo corrects measured position error.
- Electronic motors require the specified driver and feedback connections.
4Explain and apply three-phase and single-phase induction motors
Three-phase currents create a rotating magnetic field that can pull a rotor around without brushes. Follow the field, induced rotor current and torque to calculate speed, slip and useful shaft power. Starting puts different demands on the supply and the load, so compare direct, star–delta and soft starting before examining how a single-phase motor creates the phase shift it needs to get moving.
4.1 Explain the rotating field, synchronous speed and slip
Three stator windings spaced 120 electrical degrees apart carry three-phase currents. Together they produce a magnetic field that rotates around the stator at synchronous speed. The rotor follows this field because motion between the field and rotor induces current.
Set the field speed
With frequency in hertz and pole pairs,
At 50 Hz, two, four, six and eight poles give 3,000, 1,500, 1,000 and 750 rpm. At 60 Hz the corresponding speeds are 3,600, 1,800, 1,200 and 900 rpm. Count pairs in the formula: a six-pole motor has three pairs. IEC plates write rpm as min⁻¹.
Follow energy into the rotor
The rotating field sweeps past the rotor bars and induces an EMF. End rings short the bars together, allowing currents to flow. These currents experience force in the stator field and produce torque in the field's direction. A cage rotor needs no brushes or direct supply connection.
The rotor runs below field speed during normal motoring. At exactly synchronous speed, field and bars would have no relative motion, induced rotor current would disappear, and the cage would produce no torque. The fractional difference is slip:
A four-pole motor at 1,440 rpm on 50 Hz has a 60 rpm difference, so . Rotor-current frequency is . Use 0.04 in that multiplication, not the percentage number 4.
A plate marked 1,455 min⁻¹ at 50 Hz points to four poles: its nearby synchronous speed is 1,500 rpm, giving 3% rated slip. The plate reports the loaded shaft speed, not the field speed.
Recognize rotor and supply changes
A squirrel cage consists of aluminum or copper bars in a laminated core, joined by end rings. It is rugged and needs little maintenance. A wound rotor brings three rotor windings out to slip rings. External resistors can improve its starting torque while reducing starting current, at the cost of more maintenance.
Swapping any two supply phases reverses the rotating field and shaft. Moving all three leads around cyclically preserves phase sequence. Losing one line is different: a stopped motor cannot start, and a running motor may keep turning while the remaining currents rise enough to overheat it. Phase-failure-sensitive protection detects this condition.
Compare synchronous traction motors
A synchronous motor has rotor magnets or a DC-excited rotor field. It runs at field speed with zero slip. Permanent-magnet synchronous and induction motors both serve vehicle traction. An inverter sets their AC frequency and therefore field speed. During regenerative braking the machine sends mechanical energy back as electrical energy to the battery.
Key Takeaways
- Synchronous speed depends on frequency and pole pairs.
- A cage rotor needs slip to induce current and produce torque.
- Rotor-current frequency equals slip fraction times supply frequency.
- Swapping two phases reverses the rotating field.
- A synchronous motor runs with zero slip.
- Phase loss can overheat a motor that keeps turning.
4.2 Calculate the power, current and torque of a three-phase motor
The kW value on a motor plate is useful shaft output. The electrical input must also cover winding heat, iron loss, friction and windage. Keep those power stages separate before calculating current or torque.
Find input and current
For a balanced three-phase motor,
Use line-to-line voltage and line current. Efficiency and power factor are separate quantities: efficiency compares real output with real input; power factor compares real electrical power with apparent power.
A 7.5 kW motor with 90.8% efficiency needs input. At 400 V and power factor 0.84,
Ignoring both efficiency and power factor gives about 10.8 A, too low for the actual rated line current. Convert percentages to fractions before substitution.
Turn shaft power into torque
Torque equals shaft power divided by angular speed. A convenient technician form is
with output power in kW, speed in rpm and torque in N·m. At 7.5 kW and 1,455 rpm the torque is about 49.2 N·m. At the same power and 970 rpm it is about 73.8 N·m. Delivering the same energy per second through fewer revolutions requires more turning force.
Read the torque–speed curve
A cage motor begins at locked-rotor torque, can pass through a lower pull-up torque, then reaches breakdown torque before torque falls to zero at synchronous speed. The normal working point is near synchronous speed on the steep part of the curve. The motor accelerates only while its torque exceeds the load torque.
Fans and centrifugal pumps require little torque at low speed. A loaded conveyor may demand substantial torque immediately. A starter that reduces current also reduces available torque, so check the whole acceleration, not just the final operating point.
Explain current, voltage and heat
Starting current is commonly five to eight times rated current. At standstill, slip is 1 and rotor currents have the full supply frequency. A long run-up keeps these large currents flowing and heats the windings.
At no load, magnetizing current remains even though useful output is near zero. For 400 V, 6 A and 600 W input, . Full-load power factor for the example motor is 0.84. A motor much larger than its load therefore has poor power factor and efficiency.
At a given speed, torque is roughly proportional to voltage squared. A 10% voltage reduction leaves about of the torque. To carry the same load the motor develops more slip and current, increasing heat. Winding copper loss also rises with current squared. Lasting overload, blocked rotation and excessive starts all shorten insulation life; a common rule estimates that each extra 10 °C roughly halves it.
Key Takeaways
- Motor kW is shaft output; input also supplies losses.
- Rated-current calculations need both efficiency and power factor.
- At equal power, lower speed means higher torque.
- Acceleration requires motor torque above load torque.
- Starting current and prolonged overload heat windings strongly.
- Low supply voltage reduces available torque approximately with voltage squared.
4.3 Choose a starting method: direct, star–delta or soft start
Starting a cage motor draws much more current than running it. This can cause supply-voltage dips and mechanical shock. Select a starter by checking the supply current it permits and the torque the load needs throughout acceleration.
Compare starting methods
| Method | What it does | Main tradeoff |
|---|---|---|
| Direct-on-line (DOL) | Applies full line voltage through a contactor. | Full starting torque and full starting current. |
| Star–delta | Starts in star, then changes to normal delta running. | About one-third of delta DOL current and torque during star starting. |
| Soft starter | Raises voltage gradually using thyristors. | Adjustable ramp and current, with reduced starting torque. |
Star–delta is also called wye–delta. Each winding gets in star and full line voltage in delta. The winding-current reduction and the change between winding and line current combine to reduce starting line current to one third. Torque follows winding voltage squared, so it also falls to about one third.
Check that star–delta is possible
The motor must run in delta at the supply voltage, and all six winding ends must reach the starter. On 400 V, a 400/690 V Δ/Y motor qualifies. A 230/400 V Δ/Y motor must run in star on that supply: changing to delta would apply 400 V to 230 V windings.
For the 7.5 kW example, direct starting at seven times 14.2 A gives about 99 A. If DOL starting torque is twice the rated 49.2 N·m, it is about 98 N·m. Star starting gives about 33 A and 33 N·m. A load requiring 40 N·m at standstill would not accelerate in star even though the current looks attractive.
Follow the starter circuit
The main contactor supplies the winding starts. The star contactor joins the winding ends; the delta contactor makes the delta connections. Electrical and mechanical interlocks keep star and delta from closing together, which would short the supply. Remove terminal-board links when all six ends are wired to the starter.
A timer opens star before closing delta. Changeover occurs near normal speed and can create a current and torque peak. Switching too early makes that peak larger. Keep the same phase sequence through changeover.
The overload setting depends on relay location. A relay in the supply lines carries rated line current. One inside the delta circuit carries winding current, about . For 14.2 A rated line current the two settings are 14.2 A and about 8.2 A respectively.
Use a controlled voltage ramp
At half voltage, a soft starter gives roughly half the DOL starting current and one quarter of its torque. Starting voltage, current limit and ramp time must still let the machine accelerate. Soft stopping helps pumps avoid water hammer. A bypass contactor often carries running current after the ramp.
A soft starter leaves supply frequency unchanged, so it does not provide adjustable running speed. Autotransformer starters also reduce voltage; wound-rotor motors can instead use rotor resistance to obtain high starting torque with lower current.
Key Takeaways
- DOL applies full voltage and gives full starting torque.
- Star–delta needs a motor rated delta at the supply voltage.
- Star starting gives about one-third of delta DOL line current and torque.
- Interlock star and delta contactors.
- Set the overload from the current through its actual location.
- A soft starter controls voltage during starting, not supply frequency.
4.4 Explain and connect single-phase motors
A single main winding supplied with single-phase AC creates a pulsating field. It produces no starting torque on its own. An auxiliary winding displaced by 90 electrical degrees, with its current shifted in time, creates the rotating effect needed to start.
Compare single-phase arrangements
| Motor | Starting arrangement and use |
|---|---|
| Split-phase | A higher-resistance auxiliary winding gives moderate starting torque; a switch removes it near 70–80% rated speed. |
| Capacitor-start | A short-duty start capacitor gives high starting torque for pumps and compressors; it is switched out after run-up. |
| Permanent split capacitor (PSC) | A continuous-duty run capacitor remains in circuit; common in fans and circulating pumps. |
| Capacitor-start capacitor-run | Uses both capacitors for high starting torque and better running behavior. |
| Shaded-pole | A copper shading ring delays part of the pole flux; simple, low-torque small-fan motor. |
A universal motor is different: it is a series commutator motor designed to operate on AC or DC. It can exceed 10,000 rpm and drives tools and vacuum cleaners. Its brushes wear in service.
Replace and reverse correctly
A replacement capacitor needs the same capacitance, at least the original voltage rating, and the correct start or run duty. A start capacitor cannot remain energized continuously. A stuck start switch can overheat both it and the auxiliary winding. Discharge capacitors before handling their terminals.
For an accessible split-phase or capacitor motor, reverse either the main or auxiliary winding connections with the motor stopped. Reversing both preserves their relative action. Swapping line and neutral reverses both together and leaves rotation unchanged. Shaded-pole direction is fixed by construction.
Identify compressor terminals
A hermetic compressor commonly has C, S and R terminals: common, start and run. With isolated terminals, measure all three pair resistances. The largest is S–R, the sum of the two winding resistances. The terminal absent from this pair is C. From C, the lower resistance identifies R.
For 2 Ω, 5 Ω and 7 Ω readings, the 7 Ω pair is S–R; the 2 Ω winding is C–R. If both readings to C are open but S–R is continuous, an internal overload protector may be open. Allow cooling and retest before judging winding damage. Low resistance from a terminal to the body indicates an insulation fault.
Calculate power or use a Steinmetz connection
Single-phase real input is . At 230 V, 3.2 A and 0.8 power factor, input is about 589 W. At 65% efficiency the shaft receives about 383 W. Do not add the three-phase factor .
A small 230/400 V three-phase motor can use 230 V single-phase in a Steinmetz connection: connect windings in delta, feed two terminals, and connect a run capacitor between one supply terminal and the third motor terminal. A common 230 V, 50 Hz estimate is 70 µF per kW, or 105 µF for 1.5 kW. Available output and starting torque fall; output is often around 70–80% of the three-phase rating. Move the capacitor to the other supply terminal to reverse.
Key Takeaways
- An auxiliary winding and phase shift provide single-phase starting torque.
- Start and run capacitors have different duty ratings.
- Reverse one winding relative to the other, not both.
- The largest compressor resistance is between start and run.
- An open common protector can mimic open compressor windings.
- Single-phase input power is voltage × current × power factor.
- Steinmetz operation reduces available output and starting torque.
5Read motor nameplates and connect and protect motors
A motor nameplate connects the theory to a particular machine: it states the supply, connection, current, speed and operating limits that belong together. Use those values to choose the terminal links and protection, then compare resistance, current and power measurements with the expected behavior. A useful diagnosis starts by identifying what each measurement actually tests and where the protective device sits in the circuit.
5.1 Read an IEC or NEMA motor nameplate
A nameplate states the conditions under which a particular motor delivers its rating. Read voltage, connection, current and frequency together. Its kW or HP figure is mechanical output at the shaft.
Decode an IEC plate
Consider “3~ Mot. 7.5 kW, 400/690 V Δ/Y, 14.2/8.2 A, 50 Hz, 1455 min⁻¹, cos φ 0.84, IE3 90.8%, IP55, Th.Cl. F, S1”. The motor is three-phase, runs in delta at 400 V or star at 690 V, and takes the corresponding 14.2 A or 8.2 A. Each winding is designed for about 400 V.
Its 1,455 rpm speed lies below the four-pole synchronous speed of 1,500 rpm at 50 Hz, giving 3% slip. Rated shaft torque is about 49.2 N·m. The input check is ; dividing 7.5 kW by that input gives about 90.8% efficiency.
For the usual IEC Δ/Y voltage pair, the lower voltage belongs to delta and the higher to star. Their ratio is approximately . A second 60 Hz row may give different voltage, current, output and speed; a typical four-pole speed is about 1,760 rpm. Select the complete row matching the supply.
Read environmental limits
The IP code describes enclosure protection. Its first digit concerns solids and contact: 2 protects against fingers, 5 is dust-protected and 6 dust-tight. The second concerns water: 3 spray, 4 splashing, 5 jets, 6 powerful jets and 7 temporary immersion. Select washdown equipment for actual water pressure and temperature.
Thermal classes B, F and H correspond to insulation-system limits of 130 °C, 155 °C and 180 °C. Normal ratings assume cooling air no hotter than 40 °C and altitude no higher than 1,000 m; harsher conditions need derating. Class F insulation with class B temperature rise provides thermal reserve.
Duty code S1 means continuous rated operation. S2 gives a short operating time, such as 30 minutes. S3 gives an intermittent duty factor, such as 40%. Using an S2 or S3 rating continuously can overheat the motor. Efficiency classes rise from IE1 through IE2, IE3 and IE4, with IE5 for still lower losses. Read the stated efficiency for calculations.
Interpret NEMA fields
NEMA plates use HP, FLA, RPM, VOLTS, PH, HZ, frame and insulation class. One horsepower is 745.7 W, so 10 hp is about 7.46 kW. A 1.15 service factor permits 115% output under its rated conditions, with more winding heat.
The CODE letter gives locked-rotor kVA per hp. Code G is 5.6–6.29 kVA/hp: a 10 hp, 460 V three-phase motor has 56–62.9 kVA locked-rotor demand, corresponding to about 70–79 A. The DESIGN letter describes torque and current behavior; B is common for general-purpose motors. A 230/460 V NEMA plate uses a different reconnection arrangement from an IEC 230/400 V plate.
Key Takeaways
- Keep voltage, current, connection and frequency on the same rating row.
- Nameplate power is mechanical output.
- IP, thermal class and duty code describe different operating limits.
- Convert horsepower only when interpreting an HP rating.
- NEMA CODE describes locked-rotor demand; DESIGN describes performance.
5.2 Connect a three-phase motor in star or delta and set its direction
Choose the connection from the supply's line-to-line voltage and the motor plate before positioning links. Each winding must receive its rated voltage. Carry out connection work only after switching off, isolating, locking out and proving the circuit dead.
Match the supply to the voltage pair
For an IEC Δ/Y plate, connect delta when the supply equals the lower value, and star when it equals the higher value. If neither value matches, choose a suitable motor or supply arrangement.
| Motor plate | 230 V three-phase supply | 400 V three-phase supply |
|---|---|---|
| 230/400 V Δ/Y | Delta | Star |
| 400/690 V Δ/Y | Unsuitable at rated output | Delta |
In star, each winding receives line voltage divided by . In delta, each winding receives full line voltage. On 400 V, a 230/400 V motor needs star to give its windings about 231 V. Delta would overvoltage them. A 400/690 V motor needs delta there; leaving it in star gives about one third of normal torque and can cause failure to accelerate or overheating under load.
Read terminal identities
A common IEC board has U1, V1, W1 across the top and W2, U2, V2 across the bottom. The shifted order matters: the windings are U1–U2, V1–V2 and W1–W2, not the vertically adjacent pairs.
For star, join W2, U2 and V2 and connect the supply to U1, V1 and W1. For delta, link U1–W2, V1–U2 and W1–V2, then supply U1, V1 and W1. Read the actual labels before fitting links. Older machines may mark the winding pairs U–X, V–Y and W–Z.
Reconnect a NEMA nine-lead motor
For the common nine-lead wye-wound 230/460 V arrangement, high voltage joins 4–7, 5–8 and 6–9; connect the lines to 1, 2 and 3. Low voltage joins 4–5–6 together; connect L1 to 1 and 7, L2 to 2 and 8, and L3 to 3 and 9. This series/parallel reconnection has a 2:1 voltage ratio. Delta-wound nine-lead motors use other groups, so follow the machine's own diagram.
Check direction and finish the connection
With positive L1–L2–L3 sequence applied to U1–V1–W1 in the IEC convention, rotation is clockwise viewed from the drive end. A pump or scroll compressor can be damaged by wrong rotation. Check phase sequence or briefly test an uncoupled motor before coupling a direction-sensitive load.
To reverse, swap any two supply lines; leave the star or delta links in their chosen arrangement. A reversing starter uses interlocked contactors to make that swap. Connect protective earth (ground) to the frame terminal, size conductors for the current, tighten terminals correctly, and use glands, gasket and cover that maintain the enclosure's IP rating.
Key Takeaways
- Choose delta at the lower IEC voltage and star at the higher voltage.
- Use terminal labels to identify winding pairs.
- Star joins the three winding ends; delta joins each start to another winding end.
- Nine-lead NEMA wiring depends on winding construction.
- Reverse a three-phase motor by swapping two supply lines.
- Protective earth connects to the motor frame.
5.3 Protect a motor and check it with measurements
Motor protection must tolerate normal acceleration and interrupt damaging faults or lasting overload. Measurements then help distinguish electrical faults, excessive mechanical load and cooling problems.
Coordinate the protective functions
A fuse or circuit breaker clears short circuits quickly. An overload relay follows excessive current over time to protect the windings. An aM motor fuse supplies short-circuit protection only and needs overload protection alongside it. General-purpose gG fuses and suitable circuit breakers are other options.
Breaker magnetic trip ranges are approximately 3–5 times rating for curve B, 5–10 for C and 10–20 for D. A motor starting at seven times rated current can enter a curve C magnetic trip band. Select protection for starting current and fault clearance together.
Set an overload relay to the rated current for the actual connection. In supply lines, the 7.5 kW example needs 14.2 A on 400 V. Inside its delta winding circuit, the relay sees about 8.2 A. Raising the setting to suppress trips leaves the motor exposed; investigate loading, voltage, phase loss and cooling.
Trip class describes permitted operating time at high current. From cold, a class 10 relay trips between 4 and 10 seconds at 7.2 times its setting. Classes 20 and 30 allow longer acceleration. A motor protection circuit breaker combines overload and short-circuit trips with switching; phase-failure sensitivity adds protection against single-phasing.
PTC thermistors sense winding temperature directly through a thermistor relay. They detect overheating from blocked cooling or hot ambient air even without a large current increase. Current-based overload relays can account for repeated-start heating, but do not measure the winding temperature itself.
Compare insulation and winding resistance
An insulation tester measures resistance between windings and frame, and between separate windings with the links removed. Disconnect electronic starters and other sensitive equipment first. Use the manufacturer's test voltage: 500 V DC is common for 230/400 V motors; some procedures use 1,000 V for 690 V motors. Read after one minute and discharge the tested winding afterward.
Compare values at the same temperature or corrected to 40 °C. An IEEE-based minimum commonly used for low-voltage motor windings is 5 MΩ; the 1 MΩ figure used in some installation checks is a different acceptance reference. Healthy dry insulation often reads hundreds of megohms. Falling values suggest moisture, contamination or damage.
A low-resistance ohmmeter checks each winding's copper path. Readings of 2.10, 2.12 and 2.11 Ω are balanced. A much lower reading such as 1.62 Ω in one winding warrants investigation for shorted turns; an open reading points to an interrupted path or connection. Equal DC resistances alone do not establish that all turn insulation is healthy.
Check running behavior
Clamp around one line to measure its current; use inrush capture for starting current. Compare all three running currents and the motor's rating. Unbalance suggests supply, connection or winding problems. A power analyzer reads power factor directly, or calculate from real input watts and line values. Use correctly rated instruments and the safe live-measurement procedure for the circuit.
Key Takeaways
- Short-circuit and overload protection perform different jobs.
- Set the overload to the current carried at its circuit location.
- Trip class must allow the normal run-up time.
- PTCs respond directly to winding temperature.
- Insulation resistance and winding resistance test different electrical paths.
- Compare current balance, rated current and power factor when diagnosing running behavior.
Transformers and Motors examples
1Follow a transformer from core flux to rated load
13 steps
- 1IntroductionStart with the two circuits
A transformer has a supply circuit and a load circuit linked by changing magnetic flux. Picture a control panel that needs 24 V for its contactor coils while the incoming circuit supplies 400 V. We will first explain how the voltage appears, then size the turns and current, and finally check the heat and VA limits that determine whether the unit can do the job.
- 2ExplanationFollow the magnetic link
AC in the primary establishes alternating flux in the core. That flux links the secondary and induces EMF in each turn. With the secondary circuit open, voltage is present but no load current flows. Connecting a coil completes the load circuit; secondary current then causes the primary to draw extra current to maintain the flux.
This is mutual induction: energy crosses the magnetic link between the circuits.
- 3Key InsightWhy the core is laminated
The alternating core flux can induce currents in the steel itself. A solid core would allow large circulating paths and more heat. Thin steel sheets with insulation between them restrict those paths.
The closed magnetic path also keeps magnetizing current small. Opening that path makes the primary need more current to establish useful flux.
- 4ChallengePredict a frequency change
A transformer runs at fixed voltage. What happens to its required peak flux if frequency falls from 60 Hz to 50 Hz?
---reveal---
From , the flux must rise by , or 20%. The core may saturate and overheat. Applying the ratio as 50/60 would predict a fall, reversing the relationship between frequency and flux.
- 5ExampleSet up the turns calculation
A 400/24 V transformer has 1,000 primary turns. Its secondary must produce 24/400 of the primary voltage, so it needs the same fraction of the turns. Write the rearranged relationship before substituting:
The answer should be fewer than 1,000 turns because this is a step-down transformer.
- 6ExampleCalculate secondary turns
Substitute the primary turns and voltage pair:
The secondary needs 60 turns. Check the result from the other direction: 1,000/60 is about 16.7, matching 400/24. Each turn links the same changing flux, so the same volts-per-turn relationship must hold on both windings.
- 7ExampleFind current on both sides
The 24 V circuit supplies 72 VA. Its current is . The ideal primary current is .
The high-voltage side needs less current to transfer the same apparent power. A 3 A primary current would mean 1,200 VA entering a load that receives only 72 VA, so it fails the power-balance check.
- 8ChallengeCheck a control-load addition
A 120 VA, 24 V secondary already supplies 3 A. Can it supply another 2.5 A continuously?
---reveal---
The combined current would be 5.5 A, requiring . That exceeds the 120 VA rating. Its rated secondary current is only ; each coil shares this total limit.
- 9ExampleSeparate constant and load losses
Iron loss continues while the transformer is energized at its normal voltage and frequency. Copper loss changes with load current squared.
For a unit with 80 W iron loss and 200 W full-load copper loss, half rated current gives copper loss. Total loss is then 130 W. Halving current does not halve both losses.
- 10Key InsightKeep line values apart from winding values
A delta primary winding has full line voltage across it. A star secondary winding has line voltage divided by √3.
A 10 kV/400 V Dyn11 transformer therefore has about primary turns for each secondary turn on a limb. The line-voltage ratio is only 25. Reading the connections explains why these two ratios differ.
- 11ChallengeChoose the needed construction
A test circuit needs electrical separation from its supply at the same AC voltage. Would an autotransformer supply that separation?
---reveal---
No. An autotransformer uses one tapped winding, leaving a conductive path between input and output. An isolating transformer provides separate windings with double or reinforced insulation. An unchanged output voltage can still be useful when separation is the job.
- 12ChallengeCombine load and efficiency
A 5 kVA transformer at half load and unity power factor has 80 W iron loss and 200 W full-load copper loss. What is its efficiency?
---reveal---
Output is 2,500 W. Copper loss is , so input is 2,500 + 80 + 50 = 2,630 W. Efficiency is .
- 13RecapUse a consistent check order
Read the supply voltage and frequency, then identify the winding ratio and total load VA. Calculate current on each side and compare it with the ratings. For real performance, include the iron loss and the load-dependent copper loss.
On a three-phase plate, inspect the winding connections before converting line values to winding values. These checks answer different questions and prevent one plausible number from hiding a wrong connection.
2Control a generating set without mixing voltage and frequency
11 steps
Save this lesson to follow every Walkthrough step by step.
- 1IntroductionFollow energy from the shaft
- 2ExampleMake a conductor cut the field
- 3ConnectionExplain the driving torque
- 4ExplanationChoose AC or one-polarity output
- 5ChallengeCalculate from poles and speed
- 6ExplanationAssign the two control jobs
- 7ChallengeDiagnose a load step
- 8Key InsightChange the situation to a large grid
- 9ChallengeComplete the synchronization check
- 10ConnectionRecognize rectification and regeneration
- 11RecapKeep the operating situation visible
3Explain a DC motor from starting current to position control
15 steps
Save this lesson to follow every Walkthrough step by step.
- 1IntroductionA motor also generates voltage
- 2ExampleUse the motor-force rule
- 3ExampleCalculate the opposing voltage
- 4Key InsightReturn the shaft to standstill
- 5ExampleFind total starting resistance
- 6ExampleSubtract the resistance already present
- 7ChallengePredict a load increase
- 8TipReverse only one magnetic factor
- 9ExplanationCompare field-dependent behavior
- 10ConnectionMove current switching off the rotor
- 11ExampleCount steps carefully
- 12ChallengeChoose measured correction
- 13TipConnect motor and drive as a system
- 14ChallengeLink field loss with speed control
- 15RecapFollow the current before predicting motion
4Follow an induction motor through load and starting choices
20 steps
Save this lesson to follow every Walkthrough step by step.
- 1IntroductionStart with the moving field
- 2ExampleEstablish synchronous speed
- 3ExplanationInduce rotor current
- 4ExampleMeasure the speed difference
- 5ChallengeIdentify poles from a new plate
- 6ExampleFind electrical input first
- 7ExampleConvert input watts into line current
- 8ExampleFind useful shaft torque
- 9ChallengePredict a voltage dip
- 10Key InsightAsk whether the load can accelerate
- 11ExplanationCheck the star–delta rating
- 12ExampleCompare current and torque reductions
- 13ChallengeChoose a method from the limits
- 14TipPlace the overload setting in the circuit
- 15ExplanationCreate a single-phase starting field
- 16ExampleIdentify compressor leads
- 17ChallengeReverse the winding relationship
- 18ConnectionRecognize reduced-output operation
- 19ChallengeCombine speed and starting eligibility
- 20RecapConnect the field to the load
5Turn a nameplate into a connection and protection plan
14 steps
Save this lesson to follow every Walkthrough step by step.
- 1IntroductionTreat the plate as matched operating data
- 2ExampleRead the main electrical row
- 3ExplanationSeparate operating limits
- 4ChallengeCheck one reading from the plate
- 5ExampleMatch winding voltage to the supply
- 6ExplanationRead the board before fitting links
- 7ChallengeKeep the connection while reversing
- 8ConnectionRecognize a different reconnection system
- 9ExplanationAssign each protective function
- 10Key InsightSelect the appropriate measurement
- 11ChallengeUse a temperature sensor’s extra information
- 12ChallengeCombine the plate with measured currents
- 13TipBuild a diagnosis from the pattern
- 14RecapMake the decision traceable
Transformers and Motors practice questions
Set 1: Explain DC motor current and motion control10 Practice Questions
Question 1 of 10
Show answerHide answer
Question 2 of 10
Show answerHide answer
Question 3 of 10
Show answerHide answer
Question 4 of 10
Show answerHide answer
Question 5 of 10
Show answerHide answer
Question 6 of 10
Show answerHide answer
Question 7 of 10
Show answerHide answer
Question 8 of 10
Show answerHide answer
Question 9 of 10
Show answerHide answer
Question 10 of 10
Show answerHide answer
Set 2: Trace induction, voltage and generated frequency10 Practice Questions
Save this lesson to see every answer and practice every set.
Question 1 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 2 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 3 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 4 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 5 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 6 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 7 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 8 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 9 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 10 of 10
Show answerHide answer
Save this lesson to see this answer.
Set 3: Work out induction speed, power and starting torque10 Practice Questions
Save this lesson to see every answer and practice every set.
Question 1 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 2 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 3 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 4 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 5 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 6 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 7 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 8 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 9 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 10 of 10
Show answerHide answer
Save this lesson to see this answer.
Set 4: Read plates, choose links and interpret motor tests10 Practice Questions
Save this lesson to see every answer and practice every set.
Question 1 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 2 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 3 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 4 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 5 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 6 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 7 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 8 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 9 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 10 of 10
Show answerHide answer
Save this lesson to see this answer.
Set 5: Combine machine ratings with operating decisions10 Practice Questions
Save this lesson to see every answer and practice every set.
Question 1 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 2 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 3 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 4 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 5 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 6 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 7 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 8 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 9 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 10 of 10
Show answerHide answer
Save this lesson to see this answer.
Stuck on your own question? Homework Help
Key Terms
A
Alternator
aM fuse
Apparent power
Armature
Automatic voltage regulator
Autotransformer
Auxiliary winding
B
Back EMF
Breakdown torque
Brushless DC motor
Bypass contactor
C
Closed-loop control
Commutator
Compound motor
Contactor
Copper loss
Core saturation
Current transformer
D
Delta connection
Direct-on-line starter
Duty type
E
Efficiency
Efficiency class
Encoder
Excitation
G
Generator
Governor
I
Induced EMF
Inrush current
Insulation resistance
Interlock
IP code
Iron loss
L
Lamination
Locked-rotor code
M
Magnetizing current
Motor effect
Motor protection circuit breaker
Mutual induction
N
Nameplate
O
Overload relay
P
Phase loss
Phase sequence
Pole pair
Power factor
Primary winding
Protective earth
PTC thermistor
Pull-up torque
R
Rectifier
Regenerative braking
Residual magnetism
Rotating magnetic field
Run capacitor
S
Safety isolating transformer
Secondary winding
Series motor
Service factor
Servo system
Shaded-pole motor
Shaft power
Short-circuit voltage
Shunt motor
Slip
Slip ring
Soft starter
Squirrel-cage rotor
Star connection
Star–delta starter
Start capacitor
Starting current
Starting resistance
Starting torque
Steinmetz connection
Step-down transformer
Step-up transformer
Stepper motor
Synchronization
Synchronous motor
Synchronous speed
T
Thermal class
Torque
Torque–speed curve
Transformer
Trip class
Turns ratio
U
Universal motor
V
Vector group
W
Winding resistance
Wound rotor
About this lesson