Electrical Safety at Work
BeginnerLesson 6 of 7 in Electrical Principles for Technicians Course
What you will learn
- Describe how current through the body, contact with live or faulty parts, and electric arcs cause shocks, burns and blast injuries, and how to respond when someone is hurt.
- Describe how electric current affects the bodyExplain which factors set the size and effect of a current through the body, estimate it with Ohm's law, recognize the main thresholds for alternating current and respond safely to an electrical accident.
- Distinguish direct and indirect contactExplain how people touch live parts directly or through faulty equipment, why the earth completes the circuit, and how basic protection and fault protection prevent each kind of contact.
- Explain electrical burns, arc flash and arc blastDescribe how current and electric arcs cause burns and blast injuries, what starts an arc fault, and the situations in which the risk is highest.
- Describe how electric current affects the body
- Explain how protective earthing, bonding, equipment classes, fuses, circuit breakers and residual current devices work together to limit the danger when insulation fails.
- Explain earthing, bonding and equipment classesDescribe the purpose of the protective conductor and equipotential bonding, follow a fault current through an earthed appliance, and compare Class I, II and III equipment.
- Explain how fuses and circuit breakers protect circuitsDescribe overload, short-circuit and earth-fault currents, explain how fuses and miniature circuit breakers (MCBs) clear them, and explain why they protect cables and equipment rather than a person touching a live part.
- Explain how residual current devices protect peopleDescribe how an RCD detects current leaking to earth, what 30 mA additional protection achieves and does not achieve, which type suits which equipment, and how it is checked.
- Explain earthing, bonding and equipment classes
- Apply competence roles and written authorization, assess the risks of a task, and choose between dead working, live working and working near live parts, so that each job is done by the right person in the right way.
- Apply competence roles and authorizationDistinguish ordinary, instructed and skilled persons, describe written authorization and the people in control of an installation and of a work activity, and stay within the limits of your own authorization.
- Choose a safe working method and control the work areaAssess the electrical risks of a task, prefer dead working, justify live work only in defined cases, and use approach distances, barriers and collective protection when working near live parts.
- Apply competence roles and authorization
- Apply the five safety rules in order, prove equipment dead with suitable test equipment, and lock, tag and release it so that nobody can re-energize it while anyone is working on it.
- Apply the five safety rulesPrepare the job and carry out the five safety rules in the correct order before dead work, and reverse them safely when the work is finished.
- Prove equipment dead with suitable test equipmentSelect a suitable voltage tester and leads, prove it before and after testing, and test every combination of conductors at the point of work, including DC and stored-energy circuits.
- Lock out, tag out and release equipmentApply personal locks and tags to every energy-isolating device, control stored and non-electrical energy, use group lockout and shift handover, and remove locks and restore the supply in a controlled way.
- Apply the five safety rules
- Read arc flash information, relate incident energy to boundaries and arc ratings, reduce the risk, and select, check and wear electrical protective equipment correctly.
- Assess arc flash risk and reduce itUse incident energy, the arc flash boundary and equipment labels to judge arc flash risk, and explain how de-energizing, faster protection and distance reduce it.
- Select, check and use electrical protective equipmentChoose arc-rated clothing, face, head and hand protection, insulating gloves and insulated tools for the task, check them before use and wear them correctly.
- Assess arc flash risk and reduce it
Electrical Safety at Work study guide
1Explain how electricity injures people
Electricity can injure a person through current inside the body or energy released outside it. Follow the contact path to understand shock, then distinguish it from the heat and pressure of an arc fault. These differences explain why a small skin mark can hide a serious injury, why a low-voltage board can be dangerous at a distance, and why the first response to an accident must protect the rescuer as well as the casualty.
1.1 Follow the current through the body
An electric shock happens when current passes through the body. A person becomes part of a circuit by touching two points at different voltages, such as a live wire and an earthed frame. The second contact can be through the feet and floor.
Estimate the body current
Use Ohm's law with the impedance of the whole path:
Here, voltage is measured in volts, impedance in ohms and current in amperes. The path includes skin, internal tissues, footwear, gloves and the floor. Impedance changes with contact area, moisture, skin damage and voltage. Large contact areas and wet skin usually lower it. At line voltage, large dry hand contacts can give a typical adult hand-to-hand impedance of roughly 1,000–1,300 Ω; this is a sample value, not a personal rating.
For 230 V across a 1,200 Ω path:
If the impedance falls to 500 Ω, the current becomes 0.46 A, or 460 mA. Compare currents only after putting them in the same unit: 1 A is 1,000 mA. A 16 A breaker can remain closed during either shock because the body current is far below its operating current.
Current, time and path work together
At 50 or 60 Hz AC, about 0.5 mA can be felt. Around 5–10 mA, some people lose the ability to release a conductor because their muscles contract. Higher currents can interfere with breathing. These thresholds describe populations; they are not safe limits for an individual.
Ventricular fibrillation is a chaotic rhythm that stops the heart pumping effectively. A current around 40 mA can cause it after about one to two seconds; a shock lasting a few hundredths of a second generally needs several hundred milliamperes. Faster disconnection reduces exposure time. A path across the chest, such as hand to hand or hand to feet, is especially dangerous. A local path through a finger can still cause burns.
DC produces different muscle and heart effects. Its longer-duration fibrillation threshold is higher, but solar strings and battery systems can still drive fatal currents and deep burns. DC arcs are difficult to interrupt because the current has no regular zero crossing.
Read voltage names correctly
“Low voltage” includes supplies up to 1,000 V AC or 1,500 V DC. Everyday 230/400 V and 120/240 V systems sit in that range. Extra-low voltage means up to 50 V AC or 120 V ripple-free DC. Shock risk is much lower in dry conditions, but a high-current battery can still cause burns or an arc.
Respond without becoming another casualty
Do not touch someone who remains connected to electricity. Disconnect the supply safely and call emergency services; have another person call while isolation is arranged. If safe disconnection is impossible, keep clear and get trained electrical rescue help. Stay well away from fallen lines and high-voltage equipment. Once the scene is safe, follow the emergency operator's directions, begin CPR and use an AED if the person is unresponsive and not breathing normally. Arrange medical assessment after a significant shock, even when the surface injury looks small.
Key Takeaways
- Body current depends on touch voltage and total path impedance.
- Wet skin, large contacts and damaged skin can increase current.
- Current path and duration change the injury risk.
- A circuit breaker can remain closed during a fatal shock.
- DC and low-voltage supplies can be lethal.
- Make the scene electrically safe before touching a casualty.
1.2 Recognize dangerous contact
Electrical contact has two main forms. Naming the form helps identify which layer of protection has failed and which parts still need testing.
Direct contact and basic protection
Direct contact means touching a part intended to carry voltage in normal operation. Bare line terminals, exposed cable cores and an uncovered neutral terminal are examples. Neutral is a live conductor even though its normal voltage to earth is small.
Basic protection keeps people away from these parts during ordinary use. It includes conductor insulation, covers, barriers and enclosures. An IP2X cover prevents finger access to hazardous parts. Obstacles and placing parts out of reach serve only where their conditions of use are met. Removing a cover changes the exposure: the protection provided by the closed enclosure is gone.
Indirect contact and fault protection
An exposed conductive part is touchable equipment metal that is normally dead but can become live after an insulation fault. A pump housing is an example. Touching that housing after a line wire has contacted it is indirect contact.
An extraneous conductive part belongs to the surrounding building or services and can introduce a potential. A metal water pipe or structural beam can provide earth contact. Touching the faulty pump and the pipe places the body between two potentials.
| Contact | What is touched? | Main protective layer |
|---|---|---|
| Direct | A normally live conductor | Basic insulation, barriers and enclosures |
| Indirect | Equipment metal made live by a fault | Fault protection, such as earthing with automatic disconnection |
Fault protection also includes double or reinforced insulation and electrical separation. These arrangements limit the danger when basic insulation fails. A 30 mA residual current device provides additional protection; it supports the other layers and never replaces a missing enclosure or a required protective conductor.
Why the ground can complete the circuit
In most public supplies, the transformer neutral is connected to earth. Current can leave the line, pass through a person and earthed surroundings, and return to the source. A person does not have to touch neutral to receive a shock. In a 230/400 V system, line to earth is normally 230 V; in a 120/240 V split-phase supply it is normally 120 V.
Consider a lamp with an upstream break in neutral while line remains connected. The load-side neutral can rise toward line voltage through the lamp. Switching off a load or observing that it has stopped working gives no reliable information about that conductor's voltage. Test neutral as part of the absence-of-voltage checks.
Touch voltage and step voltage
Touch voltage is the difference between points the body can touch at once, such as a metal housing and the floor. Step voltage is the difference between the ground under the two feet. When fault current enters soil, nearby ground points can have different potentials.
A fallen line can therefore injure someone who never touches the line. Keep well away and contact emergency services and the network operator. Someone already close should move clear with small shuffling steps and feet close together, avoiding a long stride that spans a larger voltage difference.
Key Takeaways
- Direct contact involves a normally live part; indirect contact involves equipment metal made live by a fault.
- Neutral must be treated and tested as a live conductor.
- Basic, fault and additional protection serve different purposes.
- An earth return path can complete a shock circuit.
- Touch voltage and step voltage describe different contact paths.
1.3 Recognize arc heat and blast
Electricity can injure a worker without current passing through the worker's body. An arc inside an open switchboard can project heat, light and metal across the work area.
Separate the injuries
A contact burn comes from current heating tissue along its path. Small skin marks can hide deep damage to muscles, nerves and blood vessels. An arc burn comes from radiant energy emitted by an electric arc. Thermal burns can also come from hot surfaces, molten metal or clothing that ignites or melts onto skin.
An arc fault conducts through ionized air between live conductors or between a conductor and earth. Its sudden release of heat and light is the arc flash. The supply continues feeding the arc until it is interrupted. Temperatures can reach about 19,400 °C. Intense visible and ultraviolet light can injure eyes, and metal droplets can burn skin at a distance.
Arc blast is the pressure wave from rapidly heated air and vaporized metal. Copper can expand to tens of thousands of times its original volume when vaporized. The resulting blast can throw workers, rupture eardrums and turn covers into flying debris. Burning insulation also creates hazardous smoke.
How an arc starts
A slipped probe can bridge terminals. A dropped screw can bridge busbars. Moisture, dust or corrosion can let current track over damaged insulation. Operating worn switchgear or closing a breaker onto an existing fault can start an arc.
Test equipment can itself initiate the fault. A multimeter with its leads in the current sockets presents a low-impedance path when placed across a voltage source. An instrument with inadequate voltage or measurement-category ratings may fail during a surge. Inspect the instrument and confirm its function and lead sockets before it approaches the equipment.
What sets the severity?
Four major factors are available fault current, clearing time, distance and enclosure geometry. An open door can direct the energy from a fault toward the worker. Greater distance usually reduces the heat reaching the body. A longer arc duration increases the energy released.
The relationship with current needs care. A smaller arcing current may operate a protective device more slowly. The longer duration can outweigh the reduction in current. “Less fault current means a smaller injury” is therefore an unreliable shortcut.
Low-voltage boards at 400 V or 480 V can deliver very large currents and severe arc flashes. Battery banks can sustain DC arcs. Neither a low-voltage label nor avoiding physical contact removes these hazards.
Risk rises when live covers are removed, during probing and fault-finding, near the supply origin, and during breaker insertion or withdrawal. Dead working removes the energized source from the task. While opening, isolating and testing, the equipment is still treated as live until absence of voltage has been verified, so the task's shock and arc controls remain in place.
Key Takeaways
- Contact burns, arc burns and burns from clothing have different causes.
- Arc flash releases heat and light; arc blast produces pressure and flying debris.
- A slipped tool or incorrectly connected meter can initiate an arc.
- Clearing time, distance and enclosure geometry change exposure.
- Severe arc flash can occur on low-voltage equipment.
2Explain how earthing and protective devices protect people
Protection relies on several parts doing different jobs. A protective conductor gives fault current a return path, bonding reduces differences between touchable metal, and switching devices disconnect the supply. Learn to follow the current through a faulty appliance and interpret each device's rating. That makes it easier to see why a running appliance can hide a broken earth connection and why a breaker can stay closed during a dangerous shock.
2.1 Follow an earth fault and compare equipment classes
Protective earthing connects touchable equipment metal to a protective conductor, or PE. In North America it is called grounding, and the wire is the equipment grounding conductor. The aim is a low-impedance fault path back to the source so that protection disconnects quickly.
Follow the fault loop
International PE insulation is green-and-yellow. North American grounding conductors may be green, green with a yellow stripe, or bare. In normal use PE carries little or no current. It is never a load's spare neutral.
Suppose a line wire touches the metal case of a Class I heater. The return path is through the case and PE. With source impedance 0.15 Ω, line impedance 0.5 Ω and PE impedance 0.5 Ω:
The PE voltage drop is:
The case can therefore be about 100 V above nearby earthed metal until disconnection. Earthing provides the path; the protective device limits how long the dangerous voltage remains.
If PE breaks, the heater can still work normally. A later line-to-case fault can leave its case live without enough current to operate an overcurrent device. Visual checks and protective-conductor continuity testing find defects that normal operation hides.
Bond parts that can be touched together
Protective equipotential bonding connects extraneous metal, such as incoming metal pipes and structural steel, to the main earthing terminal. During a fault, connected parts rise toward similar potentials. This reduces the voltage across someone touching them together. Bonding and earthing serve related purposes, but bonding specifically reduces differences between parts.
Recognize the equipment class
| Class | How fault protection is provided | Recognition |
|---|---|---|
| I | Basic insulation plus PE connected to exposed metal | Protective-conductor connection |
| II | Double or reinforced insulation | Square inside a square |
| III | Supply from safety extra-low voltage, SELV | Intended for a SELV supply |
Class II tools do not need PE for their intended protection. Their housings and cables must still be intact: a crack, cut or water entry can expose hazardous parts. Class III equipment relies on a suitable SELV source that does not create hazardous voltages internally. Class 0 has basic insulation without a protective earth and is not permitted in many countries.
The return path changes the protective response
TN, TT and IT name different supply earthing arrangements. In a TT system, fault current returns through soil between the installation and source electrodes. If their resistances are 50 Ω and 10 Ω, the simplified fault current is:
That is too small to operate a 16 A breaker quickly. An RCD provides earth-fault disconnection in this example because it detects the current imbalance, even when the total current is too small for rapid overcurrent operation.
Key Takeaways
- PE provides a fault return path and must not carry a normal load return.
- A working appliance can have a broken protective conductor.
- Earthing needs automatic disconnection to limit dangerous touch-voltage duration.
- Bonding reduces voltage differences between touchable metal parts.
- Classes I, II and III use different protective arrangements.
- A soil return path may require RCD disconnection.
2.2 Read fuse and circuit-breaker behavior
Overcurrent protection limits cable heating and clears major faults. To understand its limits, distinguish a sustained overload from a low-impedance fault.
Recognize the current
An overload is too much current in an otherwise healthy circuit. A short circuit joins live conductors through a very low impedance, allowing a large fault current. An earth fault joins a live conductor to earth or equipment metal.
A 2,000 W kettle and a 2,000 W heater on a 230 V circuit draw:
That exceeds a 16 A rating, but the small overload may continue for a long time before a thermal trip. A rating is not a sharp cutoff that opens the instant it is exceeded. Trip time follows the device's time-current characteristic.
Compare the mechanisms
A fuse has an element that melts when excessive current heats it sufficiently. Industrial markings include gG for general-purpose protection and aM for motor-circuit protection. An aM fuse needs separate overload protection for the motor.
A miniature circuit breaker, or MCB, usually combines a thermal element for overloads with a magnetic element for high fault current. The thermal delay allows brief starting currents without unnecessary disconnection. North American usage usually calls this a circuit breaker.
| MCB curve | Instantaneous operating range |
|---|---|
| B | 3–5 times rated current |
| C | 5–10 times rated current |
| D | 10–20 times rated current |
For a 16 A device, these ranges are 48–80 A, 80–160 A and 160–320 A. At a 200 A earth fault, B16 and C16 devices are above their instantaneous bands. A D16 is within its band, so instantaneous operation is uncertain. Replacing a B or C device with type D to stop nuisance trips can make fault disconnection too slow.
Rating and breaking capacity answer different questions
The current rating describes the circuit current the device is intended to carry. Breaking capacity is the greatest fault current it can interrupt safely, commonly 6 kA or 10 kA for an MCB and much higher for some industrial fuses. A device exposed to a fault above its breaking capacity can fail violently.
Replace a fuse with the same type, current rating and breaking capacity. Never bridge it or fit a larger rating to avoid repeated operation. Reset an MCB only after the cause has been addressed and within the employer's authorization. Closing repeatedly onto an unknown fault can initiate an arc flash.
Why a dangerous shock may not trip it
A body current of 190 mA is only 0.19 A, far below 16 A. A fuse or MCB can therefore remain closed while a person receives a fatal shock. It contributes to fault protection when a PE path permits enough current for fast disconnection. Basic protection prevents contact with live parts, and a sensitive RCD adds protection against earth-leakage shock.
Key Takeaways
- An overload and a short circuit produce different trip behavior.
- An MCB has thermal and magnetic trip mechanisms.
- B, C and D curves have different instantaneous operating bands.
- Breaking capacity is distinct from the normal current rating.
- A fuse or breaker can remain closed during a dangerous body current.
2.3 Understand what an RCD detects
A residual current device, or RCD, detects current returning by an unintended path. It compares the instantaneous currents in all live conductors passing through its sensing core, including neutral when present.
Follow the balance
In a healthy circuit the magnetic effects cancel because the current sum is zero. In a single-phase circuit, current leaving on line equals current returning on neutral. Leakage through PE or a person makes the sum unequal.
For a line current of 10.03 A and a neutral return of 10.00 A:
A 30 mA RCD must operate at its rated residual current. It must not operate at or below half that value, 15 mA; between those points it may operate. It does not wait for the load current to reach 30 mA—the load may already carry many amperes. It responds to the imbalance.
Understand time and protection limits
A general, non-delay RCD has a maximum operating time of 300 ms at its rated residual current and 40 ms at five times that value. For a 30 mA device, the latter test current is 150 mA. Type S devices deliberately delay operation to coordinate with downstream protection and are not used for additional personal protection.
The RCD limits shock duration. It does not limit the initial current through a person to 30 mA. Current still follows the voltage and body-path impedance until the contacts open. Fast disconnection reduces the likelihood of a fatal heart rhythm but does not guarantee that no injury occurs.
If a person bridges line and neutral while insulated from earth, the current can leave through line and return through neutral in balance. The RCD then has no residual signal. The same limitation applies to a line-to-line path. Basic insulation and covers remain essential.
North American personnel protection uses a GFCI, a ground-fault circuit interrupter. A Class A GFCI must operate at 6 mA and must not operate below 4 mA. A 30 mA IEC RCD and a Class A GFCI therefore have different thresholds.
Match the device to the circuit
An RCCB provides residual-current protection without overload protection. It needs a fuse or breaker in series. An RCBO combines residual-current and overcurrent protection.
| RCD type | Leakage waveform it detects |
|---|---|
| AC | Sinusoidal AC |
| A | AC and pulsating DC |
| F | Adds mixed-frequency currents |
| B | Also detects smooth DC |
Power electronics in drives, chargers and inverters can create DC leakage. An unsuitable RCD may be blinded, so use the type required for the equipment.
Press the test button at the manufacturer's or local rule's interval. It creates an imbalance to check the mechanism. Measuring actual trip current and trip time requires an RCD tester. Repeated tripping calls for fault investigation, including moisture, damaged insulation and accumulated leakage; never bypass the protection to keep equipment running.
Key Takeaways
- RCDs detect a nonzero current sum in the live conductors.
- A 30 mA rating is a residual-current threshold, not a body-current limit.
- Balanced line-to-neutral contact can escape RCD detection.
- An RCCB needs separate overcurrent protection; an RCBO includes it.
- RCD waveform type must suit the equipment.
- The test button checks operation but does not measure trip time.
3Organize electrical work with the right people and methods
Electrical safety starts before anyone opens an enclosure. The assigned people need the skills, permission and information for the actual task, and the work area needs controls that match the exposure. Connect competence roles with the choice of dead work, live work or work near live parts. Then use barriers, approach limits and a clear briefing to keep both the work team and other people protected as conditions change.
3.1 Match the job to the person's authority
Knowing how to carry out a task and being allowed to carry it out are separate requirements. Electrical work assigns both the people who do the job and the people who control its safety.
Understand competence levels
EN 50110-1 distinguishes ordinary, instructed and skilled persons. An ordinary person is neither instructed nor skilled in electrical work. They use equipment intended for ordinary users and keep enclosures closed.
An instructed person has received suitable advice or supervision from skilled people to recognize and avoid hazards in assigned tasks. Their role can include a defined switching operation or lamp replacement after safe isolation. It does not give general permission to repair installations.
A skilled person has the electrical education, knowledge and experience to assess the work's risks and avoid its hazards. They can plan isolation and safety measures within their own authorization. Familiarity with one installation does not establish competence for every installation.
In US practice, OSHA and NFPA 70E use qualified person for someone who has demonstrated relevant equipment knowledge and skills and received training to recognize and avoid the hazards. Qualification is task- and equipment-specific. A technician qualified for a small control panel may be unqualified for high-voltage switchgear.
Read the authorization
Competence describes capability. Authorization is the employer's permission to do specified work. It normally records the person's name, covered installations and tasks, restrictions and validity. A course certificate is evidence that can support the assessment; it is not the employer's permission by itself.
For example, a maintenance worker's authorization covers resetting breakers after an approved check and replacing lamps. The worker notices a scorched terminal behind a distribution-board cover. The repair is outside those tasks. The worker stops, protects others from the defect and reports it to the skilled person responsible. Having repaired a similar terminal elsewhere does not extend the authorization.
Know who controls what
| Role | Main responsibility |
|---|---|
| Person in control of the electrical installation | Safe operation, switching, isolation and earthing arrangements |
| Person in control of the work activity | The task, team briefing, work zone and on-site safety measures |
The two agree the work zone and protective measures before work begins. The installation is released for work only after the required conditions are established. On a small job, one person may hold both roles; the responsibilities still need to be carried out.
Make supervision and briefings effective
Supervision must be close enough for the risk and the worker's needs. A skilled person elsewhere on site who cannot observe or intervene may not provide the required supervision.
The briefing identifies the task, hazards, isolation points, work limits and responsible people. Repeat it when a new crew arrives, the work expands or conditions change. An unexpected source, damaged enclosure or different piece of equipment is a reason to stop and reassess with the responsible person before continuing.
Key Takeaways
- Competence and employer authorization are separate requirements.
- Instructed persons carry out defined tasks within their instructions.
- Qualification depends on the task and equipment.
- The installation role and work-activity role have distinct responsibilities.
- Changes in people or conditions require a renewed briefing.
3.2 Choose the working method and protect the area
Start a job by identifying what can harm people and how the work could create exposure. A risk assessment connects the equipment, task, environment and people to a safe working method.
Assess before choosing controls
Identify live parts, possible back-feeds, voltage and available fault energy. Consider wet surfaces, cramped access, nearby work, lighting and escape routes. Check the competence and authorization of the people assigned. A routine written procedure can cover repeated work under unchanged conditions; a changed condition needs a fresh assessment.
EN 50110-1 describes three methods:
| Method | What it means |
|---|---|
| Dead working | The work area is isolated and secured using the five safety rules |
| Live working | The body, a tool or equipment contacts live parts or enters their live working zone |
| Work in the vicinity | Work is near live parts while remaining outside the live working zone |
Dead working is the normal choice. Live work requires a valid reason, such as a greater hazard from shutdown or a measurement that requires the circuit energized. Lost production and convenience do not justify it. It requires task-specific training, an approved procedure or permit, suitable tools and PPE, and the required accompaniment.
Use the strongest controls first
Eliminate exposure by isolating. Where useful, substitute a lower hazard, such as remote operation or an extra-low-voltage tool. Add engineering controls such as rigid barriers, finger-safe terminals and insulating covers. Administrative controls include permits, procedures, warning signs and supervision. PPE is the final layer.
Collective measures protect people across the area. Covering a live terminal prevents accidental contact by several workers; gloves protect their wearer. Barrier tape identifies a limit but provides no insulating cover over a terminal. Keep the area dry, clear and well lit, and remove conductive jewelry before the work.
Apply approach limits to people and tools
For exposed fixed AC parts in the NFPA 70E 151–750 V range, the limited approach boundary is about 1.0 m and the restricted approach boundary about 0.3 m. For exposed movable conductors in that range, limited approach is 3.0 m. These are shock boundaries; the arc flash boundary is determined separately.
An unqualified person crosses the limited boundary only with a qualified person's escort and advice. Entry within the restricted boundary requires a qualified person with the plan and shock protection. Assess the nearest body part and tool tip, not just where the person's feet stand.
At 0.5 m from exposed fixed 400 V busbars, a worker is inside limited approach but outside restricted approach. A screwdriver reaching to 0.2 m changes that: the tool crosses restricted approach.
Protect live parts that remain nearby
A contactor's circuit may be isolated while a separate incoming supply remains live. Prove the contactor circuit dead, shroud the incoming terminals and define the work zone. The nearby supply still needs its own controls. Keep cleaners, painters and other workers clear of open boards. For overhead lines, use the network operator's task-specific distances and permits.
Key Takeaways
- Assess the task, equipment, environment and people before work.
- Dead working is the normal method; production pressure is not a live-work justification.
- Use elimination and engineering controls before relying on PPE.
- Approach limits apply to tools as well as bodies.
- Shock and arc flash boundaries are determined separately.
- Isolated equipment may still have adjacent live parts.
4Make equipment safe before work
Stopping a machine changes its operation; making it safe changes every route by which energy can reach the work. Build that safe condition in a deliberate order: identify sources, disconnect, secure, verify and apply the remaining protections. Learn how a proven tester and personal locks support different parts of the process, then follow the checks needed to hand work over or restore the equipment without exposing anyone.
4.1 Apply the five safety rules in order
Safe isolation begins with identifying the exact equipment and every possible source. Use drawings, labels and a site check with the responsible person. A label can be wrong, so identification and electrical verification must agree.
Disconnect and secure
1. Disconnect completely. Separate the work circuit from every supply using devices suitable for isolation. Include standby generators, UPS units, PV systems, batteries and separate control supplies. Disconnect all line conductors and the neutral where required. A removed plug or fuse must stay under the worker's control.
An emergency stop, PLC output or contactor is a control function. It can stop movement while terminals remain live. Use an isolator, switch-disconnector or breaker designed for isolation.
2. Secure against reconnection. Apply a personal lock and warning tag to the isolating device. Keep its key. Disable auxiliary power that could operate a motorized switching device. A tag communicates the restriction; the lock physically prevents operation.
Verify before contact
3. Verify absence of operating voltage. Test at the exact point of work using a suitable tester proven before and after the test. Check every relevant conductor pair. Until verification is complete, treat the equipment as live and use the assessed protection.
Isolation separates the supply, locking preserves that separation, and testing checks the actual electrical condition. None of these steps can stand in for another.
Apply the remaining protections where needed
4. Earth and short-circuit. Apply suitably rated earthing and short-circuiting equipment where required: high-voltage work and low-voltage work with a risk of re-energization or induced voltage. Connect the earth end first, then the conductors. This keeps the work area near earth potential and creates a fault path if accidental energization occurs. Remove conductor connections first and the earth end last.
5. Protect against adjacent live parts. Cover nearby live parts with suitable insulating shrouds or blankets and establish barriers and work-zone markings. Rules 1–3 apply to every isolation. Rules 4–5 depend on the assessed situation.
Work through a drive-fed motor
A 400 V motor fed by a variable-speed drive needs terminal work. Identify the motor, drive and all supplies. Open the drive's lockable isolator and apply locks and tags. The drive's capacitors can remain charged after disconnection, so wait the stated discharge time.
Verify the absence of voltage at the motor terminals between all conductors, and check the drive's DC circuit if the work exposes it. Apply earthing and short-circuiting if the assessment requires it; it is normally unnecessary for this isolated motor without a re-energization or induction risk. Shroud adjacent live panel parts. Work begins after the responsible person releases the equipment.
Restore in a controlled sequence
Finish the job, remove tools, refit covers and guards, and check everyone is clear. Inform affected people. Remove temporary protection in the controlled reverse sequence, including conductor-side earth connections before earth-side connections. Each worker removes their own lock under the release procedure. Re-energize under the responsible person's control and perform the planned functional check.
Key Takeaways
- Identify every source before disconnecting.
- Apply disconnect, secure and verify to every isolation.
- Earth and short-circuit where the assessed situation requires it.
- Protect nearby live parts that remain energized.
- Control stored energy and obtain release before starting work.
- Restore the equipment only after the area and people are ready.
4.2 Use a tester to establish absence of voltage
An absence-of-voltage test establishes the condition of the conductors you will touch. A stopped motor, dark display or silent non-contact indicator is not enough evidence to begin work.
Select and inspect the tester
Use a suitable two-pole voltage tester or an approved multimeter set to voltage. Confirm the AC or DC function, voltage rating, lead sockets and measurement category. A non-contact voltage pen can provide an extra warning but can miss shielded conductors or DC and may have a dead battery.
| Location | Typical measurement category |
|---|---|
| Supply origin and service entrance | CAT IV |
| Distribution boards and fixed equipment | CAT III |
| Plug-in equipment | CAT II |
Match both category and voltage. A high voltage marking alone does not establish suitability at a distribution board. Inspect the casing, leads and connectors. Probe tips need insulation and finger barriers; GS38 guidance limits exposed tips to 4 mm, preferably 2 mm or less, or uses spring-loaded shrouds. Leads need suitable current limitation or fusing.
Prove, test, prove
- Prove the complete tester and leads on a proving unit or known live source.
- Test at the point of work after isolation and securing.
- Prove the tester again on the same known source.
If the final proof fails, treat the circuit as live, replace or correct the test equipment and repeat the entire sequence. A failure may have developed during the test. Before isolation, confirming voltage at the intended work point also helps detect a mistaken circuit identity.
Check every conductor pair
L means line; N means neutral; PE means protective conductor. A three-phase supply has L1, L2 and L3, with N where provided. Test live conductors against one another and against PE. Testing only line to neutral can miss a live neutral or an unexpected source.
For three conductors, L, N and PE, test L–N, L–PE and N–PE: three pairs. For L1, L2, L3 and PE there are six pairs. With neutral added, there are ten:
- L1–L2, L1–L3 and L2–L3;
- L1–N, L2–N and L3–N;
- L1–PE, L2–PE and L3–PE;
- N–PE.
For a set of conductors, the pair count is:
Test at the work terminals. A dead result at the isolator leaves uncertainty about wrong labels, borrowed neutrals and back-feeds at the actual job.
Include stored energy and DC
Drive capacitors, power supplies and long cables can retain charge. Wait the equipment's stated time, then measure at the relevant terminals, including DC capacitor terminals where exposed. Use the specified discharge equipment when required. Waiting alone does not establish zero voltage.
A lit PV module keeps producing voltage even when the inverter is isolated. A battery's cells remain a source even when its output circuit is disconnected. Use DC-rated test equipment and the specific isolation procedure, protect exposed terminals and verify the exact work point. A zero reading is useful only with correct identification, a suitable proven tester and complete conductor checks.
Key Takeaways
- Match voltage, category and AC/DC suitability to the test location.
- Prove the tester before and after testing at the work point.
- Repeat the sequence if the final proof fails.
- Check all conductor pairs, including neutral and PE.
- Stored charge and DC sources need specific checks.
- A non-contact indicator alone is insufficient for proving dead.
4.3 Keep every worker protected by lockout
Lockout keeps an isolating device from operating while people work. Tagout warns others and identifies the person responsible. A tag gives information but does not provide a physical restraint.
Control the energy, not the command
An energy-isolating device physically separates or restrains energy. Examples include a disconnect switch, suitable breaker, fuse carrier, air valve and mechanical block. A selector switch, emergency stop or PLC command acts on a control circuit and is unsuitable as the lockout point.
Use locks and tags together. If a device cannot accept a lock, the approved tagout procedure needs additional measures that provide equivalent safety, such as another disconnect or removal of a circuit element. A tag alone on an available lock point leaves the control incomplete.
Follow the sequence
Prepare by identifying energy types, hazards and isolation points. Tell affected operators, shut down normally, operate every energy-isolating device, then apply locks and tags. Release or restrain stored energy before verifying the isolation.
A machine can contain electrical charge, trapped air or hydraulic pressure, stretched springs, turning flywheels, raised loads and heat. A supply lock does not release these. Vent pressure, block falling parts and control each energy source by the approved method.
Verification includes trying the normal start control where appropriate and returning it to off, plus testing exposed electrical parts for absence of voltage. Failure to start checks the control response; electrical testing checks the voltage condition.
Give each person personal control
Every worker applies their own personal lock and keeps its key. A multiple-lock hasp allows several personal locks on one isolator. Reconnection remains blocked until the last lock is removed.
For group lockout, isolation-lock keys can be secured in a lockbox. Each worker locks the box personally, so no one can retrieve those keys while a worker remains protected. A designated coordinator checks the group arrangement and accounts for everyone joining or leaving.
At shift handover the incoming person's lock goes on before the outgoing person's lock comes off. Maintain continuous protection throughout the transfer.
Apply it to two energy sources
Three technicians service a conveyor with a 400 V drive and a pneumatic gate. They isolate and lock the electrical supply, isolate the air supply and vent trapped pressure. Each technician applies a lock at both points through the agreed hasps. After a start attempt with controls returned to off, a qualified worker verifies absence of voltage at the motor. Work can then be released under the agreed procedure.
Release the machine safely
Inspect the completed work, remove tools and restore guards and covers. Account for people, clear the area and inform affected operators. Each person removes their own lock. Restore energy under the responsible person's control and carry out the functional check.
If a worker has left without removing a lock, use the employer's exceptional-removal procedure. It includes confirming they are off site, making reasonable efforts to contact them and ensuring they know about removal before returning to work. Production urgency does not authorize a coworker to cut the lock off.
Key Takeaways
- Lock energy-isolating devices, including non-electrical sources.
- Every worker keeps personal control of their lock.
- A group lockbox must preserve each worker's protection.
- Stored energy must be released or restrained and isolation verified.
- Shift handover must leave no gap in protection.
- Exceptional lock removal follows the employer's procedure.
5Protect yourself against arc flash
Arc flash protection begins with understanding the task and the information on the equipment label. A heat-energy value belongs to a working distance, while a glove class belongs to a voltage. Use these distinctions to select the complete protective system and recognize when a changed supply or worn breaker makes an assessment unreliable. Faster clearing, remote operation and proper maintenance can reduce exposure before clothing is needed.
5.1 Use the arc label and reduce exposure
An arc assessment gives information for a specific task and equipment condition. Use its working distance, boundary and protection method together when planning the work.
Understand energy and the boundary
Incident energy is heat delivered per unit area at a specified distance. Labels commonly use cal/cm². One cal/cm² equals 4.184 J/cm². The arc flash boundary is the distance where exposure falls to 1.2 cal/cm², about 5.0 J/cm², the conventional onset level for a second-degree burn on bare skin.
The arc flash boundary can extend beyond the shock boundaries. Someone can be outside the shock contact zone while still exposed to enough radiant heat to need arc-rated PPE. People entering the assessed arc exposure area need the required protection.
Keep the two PPE methods distinct
An incident energy analysis calculates exposure from fault current, clearing time, distance and equipment configuration. Engineers perform the study; technicians use its results. The alternative PPE category method assigns a category and boundary from tables for listed equipment and tasks. Its fault-current, clearing-time and working-distance limits must all be met.
The category method does not calculate the exact incident energy of the equipment. Do not turn an analysis result into a category merely by rounding it up to a category's minimum clothing rating.
Read the complete label
A label gives nominal voltage, arc flash boundary and either incident energy at a working distance or PPE category information. For example: “400 V; boundary 1.4 m; incident energy 6.2 cal/cm² at 455 mm.”
At 455 mm, the clothing system must be rated at least 6.2 cal/cm², about 25.9 J/cm². An 8 cal/cm² system meets that thermal rating; a 4 cal/cm² shirt does not. This comparison selects the clothing rating, not the whole PPE ensemble. Hands or other parts closer to the source may face higher exposure and need separate attention.
Reduce the energy reaching the worker
Dead working removes the energized source from the work. Until testing establishes absence of voltage, opening covers, isolation and verification still need the assessed protection.
For the same arc, heat exposure is roughly proportional to duration. Reducing clearing time from 0.5 s to 0.05 s gives about one tenth of the energy. Current-limiting fuses, approved maintenance settings and arc-detection relays can shorten exposure.
Distance also helps. In an open-air approximation, doubling distance reduces energy to about one quarter: 8 cal/cm² at 455 mm becomes about 2 cal/cm² at 910 mm. Enclosures can focus energy and change that relationship. Use remote switching, remote racking and remote testing where planned; do not recalculate a board's label with the open-air shortcut.
Check whether the information remains valid
A changed transformer, protection setting or clearing time can change exposure. Poor maintenance can delay tripping. Update the analysis after relevant changes and review it at least every five years under NFPA 70E. A label does not stay reliable merely because it is still attached to the door.
Key Takeaways
- Incident energy always belongs to a stated working distance.
- The arc flash boundary is based on 1.2 cal/cm² of heat exposure.
- Analysis and category tables are alternative PPE selection methods.
- Clothing rating must meet or exceed assessed exposure at the applicable distance.
- Faster clearing and greater distance can reduce exposure.
- Equipment changes and maintenance condition can invalidate label assumptions.
5.2 Select and inspect the complete protective system
Electrical PPE must address both arc heat and electric shock. A garment's arc rating describes heat performance; a glove's voltage class describes electrical insulation. One marking cannot stand in for the other.
Select arc-rated protection
An arc rating may be given as ATPV or EBT. ATPV describes the incident energy associated with a 50% probability of heat transfer sufficient for the onset of a second-degree burn. EBT relates to fabric breakopen. These are test results, not guarantees of injury-free exposure. Select a tested clothing system with an arc rating at least equal to the assessed incident energy.
| PPE category | Minimum arc rating |
|---|---|
| 1 | 4 cal/cm², about 16.7 J/cm² |
| 2 | 8 cal/cm², about 33.5 J/cm² |
| 3 | 25 cal/cm², about 104.6 J/cm² |
| 4 | 40 cal/cm², about 167.4 J/cm² |
Use categories when the approved category method applies. Categories 1–2 use arc-rated shirt and pants or coveralls, with the prescribed face protection; category 2 needs a balaclava with the face shield or a hood. Categories 3–4 use an arc flash suit and hood. Include an electrically insulating hard hat, safety glasses and hearing protection. Above 4 cal/cm², use leather or dielectric footwear, or an alternative tested to resist ignition, melting and dripping at the assessed exposure. Follow the selected method's full footwear requirements.
Categories 1–2 allow heavy-duty leather, arc-rated, or insulating rubber gloves with protectors. Categories 3–4 require arc-rated gloves or insulating rubber gloves with protectors. Where shock exposure exists, the gloves must also have the correct voltage class. European APC 1 and APC 2 box-test classes describe different tests, at 4 kA and 7 kA; they are not cal/cm² ratings.
Match insulating gloves to voltage
Maximum AC use voltages are 500 V for class 00, 1,000 V for class 0, 7,500 V for class 1, 17,000 V for class 2, 26,500 V for class 3 and 36,000 V for class 4. A 230/400 V system can use class 00 or higher; a 690 V system needs class 0 or higher. Use a glove class and AC/DC rating suitable for the actual task.
Wear protectors over insulating rubber gloves to resist cuts and heat. Leather protectors alone provide no shock insulation. Before each use, inspect the rubber, carry out an air test for leaks and check the electrical test date. Periodic electrical retesting is commonly every six months. Reject cracked, swollen, punctured or overdue gloves and store sound gloves unfolded, away from sunlight, heat and sharp objects.
Wear the system correctly
Close garments and keep sleeves down. Choose natural-fiber or arc-rated underlayers and suitable outer layers. Melting synthetics, an ordinary rain jacket or an unrated vest can worsen burns. Protect face and neck with the required arc-rated shield and balaclava or hood, with safety glasses underneath and ear inserts.
Inspect insulated tools. IEC 60900 tools are marked with the double-triangle symbol and rated up to 1,000 V AC or 1,500 V DC. Damaged insulation takes the tool out of service; tape is not a repair. Mats and insulating footwear add protection, while isolation remains the primary control. Arc PPE mainly limits heat injury and offers limited protection against blast and flying debris.
Key Takeaways
- Arc rating and voltage class protect against different hazards.
- Use the assessed PPE method and the complete required ensemble.
- Inspect and air-test insulating gloves before use and check their test date.
- Leather protectors resist damage but do not provide shock insulation.
- Wear suitable layers with closures fastened and sleeves down.
- Reject damaged insulated tools and PPE.
- Arc PPE has limited protection against blast and flying debris.
Electrical Safety at Work examples
1Trace the injury path
12 steps
- 1IntroductionStart with the route
A damaged electrical item can expose people in different ways. Current may pass through the body, faulty metal may become live (indirect contact, unlike direct contact with a part meant to be live), or an arc may project heat across a gap (its flash and blast).
Follow each route separately. The route explains both the injury and the protection needed, including why a breaker can stay closed during a dangerous shock and why standing clear of conductors leaves an arc hazard.
- 2ExplanationThe body completes a circuit
A shock needs a potential difference and a complete current path. One hand can touch a live conductor while the feet or other hand provide the return through earthed surroundings.
The whole path has impedance: skin, internal tissues, footwear and contacts all contribute. Moisture and larger contacts can reduce it. The circuit rating does not set the body current; touch voltage and total path impedance do.
- 3ExampleChoose the complete path value
Consider a 100 V contact with a stated total path impedance of 2,500 Ω. The value already includes the body and external contacts.
Use that whole-path value in Ohm's law:
There is no need to add another guessed body resistance. Adding an extra resistance would change the stated situation and understate the current.
- 4ExampleCalculate and convert
The quotient is 0.040 A. Convert amperes to milliamperes by multiplying by 1,000:
That is far below a 16 A circuit rating but is a dangerous body current. If the path crosses the chest and lasts long enough, it can disturb the heart. Do not compare 40 directly with 16; the first number is in milliamperes and the second in amperes.
- 5ChallengeWhat changes when contacts become wet?
The 100 V contact stays the same, but the total path impedance falls from 2,500 Ω to 1,250 Ω. What happens to the current?
---reveal---
It doubles to 0.080 A, or 80 mA. The voltage is unchanged and the impedance is halved, so twice the current can flow. The breaker rating has not changed, but the body exposure has become more severe.
- 6ExplanationName the touched part
A bare terminal is intended to be live. Touching it is direct contact. A motor frame is normally dead; if insulation fails and line touches it, touching that frame is indirect contact.
Insulation and covers provide basic protection. Earthing with disconnection provides one form of fault protection. A nearby metal water pipe can complete the return path when someone touches the faulty frame.
- 7ChallengeA stopped lamp and its neutral
A lamp stops after its neutral breaks upstream, while line remains connected. Is the lamp-side neutral safe to touch, and why?
---reveal---
No. It can rise toward line potential through the connected lamp. Neutral remains a live conductor that needs testing. The lamp being dark describes its operation; it does not establish the voltage at the neutral terminal.
- 8ExplanationSeparate flash from blast
An arc fault carries current through ionized air. The flash releases intense heat and light; the blast is the pressure wave from rapidly heated air and vaporized metal.
Radiant heat can burn a person who touches no conductor. Pressure can throw the person or project fragments. Ordinary eye protection alone does not cover all of these hazards, and burning or melting clothing can deepen the injuries.
- 9ConnectionFollow current and clearing time
A lower arcing current can take longer to operate a protective device. The arc then continues releasing energy for longer.
Compare the current and duration together, along with distance and enclosure shape. A low-voltage board can supply a severe arc because it has substantial fault current available. An open cabinet can direct the heat and debris toward the person in front of it.
- 10ChallengeDoes avoiding contact remove every hazard?
A worker says, “I will keep my hands off the conductors while probing this energized board, so shock and burns are both controlled.” What is missing?
---reveal---
A slipped probe can initiate an arc, releasing heat and blast without a body contact path. Avoiding touch addresses only part of the exposure. The task still needs the approved working method, suitable testing equipment and the assessed shock and arc controls.
- 11TipProtect the rescuer first
If a person remains connected to electricity, keep hands off and safely disconnect the source. Call emergency services; another person can call while isolation is arranged. If safe disconnection is unavailable, keep clear and get trained electrical rescue help.
Once safe, follow the operator's directions and begin CPR and AED use for an unresponsive person who is not breathing normally. Significant shocks need medical assessment.
- 12RecapCheck route, time and energy
Ask where current could flow and what energy could reach the person. Body current depends on voltage, path impedance and duration. Direct and indirect contact call for different protective layers. Arc heat and blast remain possible without physical contact with a conductor.
2Follow the fault through the protection
14 steps
Save this lesson to follow every Walkthrough step by step.
- 1IntroductionGive each protective part its job
- 2ExplanationFind the fault return path
- 3ExampleAdd the loop parts
- 4ExampleFind current and case voltage
- 5ChallengeWhat if PE breaks?
- 6Key InsightCompare equipment classes
- 7ExplanationSeparate the two breaker responses
- 8ExampleApply the bands to a fault
- 9ChallengeTwo different markings
- 10ExplanationSense a missing return
- 11ExampleCalculate only the difference
- 12ChallengeWhen is the residual zero?
- 13ChallengeChoose protection for a soil return
- 14RecapTrace before you trust
3Plan a task beside live parts
10 steps
Save this lesson to follow every Walkthrough step by step.
- 1IntroductionDefine the job before opening
- 2ExplanationSeparate skill from permission
- 3ExampleAgree who controls the work
- 4ChallengeA worker reaches their limit
- 5ExplanationChoose dead working
- 6TipBuild controls in order
- 7ExampleCheck the nearest tool point
- 8ChallengeIs a permit enough?
- 9ChallengeThe task expands
- 10RecapKeep people, method and limits aligned
4Isolate, test and hand over a machine
18 steps
Save this lesson to follow every Walkthrough step by step.
- 1IntroductionBuild a safe work condition
- 2ExplanationIdentify the exact work points
- 3ExampleDisconnect the supplies
- 4ExplanationSecure the disconnection
- 5ChallengeChoose the next rule
- 6ExplanationAllow stored charge to discharge
- 7TipSelect the test system
- 8ExampleFirst prove the tester
- 9ExampleTest all the pairs
- 10ExampleProve again after the checks
- 11ChallengeFind the missing test
- 12ConnectionTreat DC sources as sources
- 13ExplanationGive every worker control
- 14ExampleControl the air supply too
- 15ChallengeMaintain protection at handover
- 16TipPrepare for restoration
- 17ChallengeRelease the complete work zone
- 18RecapKeep the safe condition through the whole job
5Read the label and select protection
12 steps
Save this lesson to follow every Walkthrough step by step.
- 1IntroductionRead the full exposure information
- 2ExplanationSeparate the two boundaries
- 3ExampleKeep distance with the energy value
- 4ExampleSelect the clothing rating
- 5ChallengeThe worker moves closer
- 6Key InsightChoose one valid selection method
- 7ConnectionReduce duration and increase distance
- 8ExplanationSelect hand protection for voltage
- 9ChallengeA 690 V hand-exposure task
- 10TipInspect and wear the full system
- 11ChallengeA complete rating still needs a safe method
- 12RecapTie the protection to the actual task
Electrical Safety at Work practice questions
Set 1: Recognize hazards and protective limits10 Practice Questions
Question 1 of 10
Show answerHide answer
Question 2 of 10
Show answerHide answer
Question 3 of 10
Show answerHide answer
Question 4 of 10
Show answerHide answer
Question 5 of 10
Show answerHide answer
Question 6 of 10
Show answerHide answer
Question 7 of 10
Show answerHide answer
Question 8 of 10
Show answerHide answer
Question 9 of 10
Show answerHide answer
Question 10 of 10
Show answerHide answer
Set 2: Plan the work and establish isolation10 Practice Questions
Save this lesson to see every answer and practice every set.
Question 1 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 2 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 3 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 4 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 5 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 6 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 7 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 8 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 9 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 10 of 10
Show answerHide answer
Save this lesson to see this answer.
Set 3: Check isolation and interpret exposure10 Practice Questions
Save this lesson to see every answer and practice every set.
Question 1 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 2 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 3 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 4 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 5 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 6 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 7 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 8 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 9 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 10 of 10
Show answerHide answer
Save this lesson to see this answer.
Set 4: Make decisions across the complete job10 Practice Questions
Save this lesson to see every answer and practice every set.
Question 1 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 2 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 3 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 4 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 5 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 6 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 7 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 8 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 9 of 10
Show answerHide answer
Save this lesson to see this answer.
Question 10 of 10
Show answerHide answer
Save this lesson to see this answer.
Stuck on your own question? Homework Help
Key Terms
A
Arc blast
Arc duration
Arc fault
Arc flash
Arc flash boundary
Arc rating
ATPV
Authorization
B
Back-feed
Body-path impedance
Breaking capacity
C
Class I equipment
Class II equipment
Class III equipment
Collective protection
Contact burn
D
Dead working
Direct contact
E
Earth fault
Earthing and short-circuiting
EBT
Electric shock
Energy-isolating device
Equipotential bonding
Exposed conductive part
Extra-low voltage
Extraneous conductive part
F
Fuse
G
GFCI
Group lockbox
I
Incident energy
Incident energy analysis
Indirect contact
Instructed person
Insulated hand tool
Insulating glove class
Isolation
L
Leather protector
Let-go threshold
Limited approach boundary
Lockout
Low voltage
M
Measurement category
Miniature circuit breaker
N
Non-contact voltage indicator
O
Overload
P
Person in control of a work activity
Personal lock
PPE category method
Protective conductor
Protective earthing
Prove–test–prove
Proving unit
Q
Qualified person
R
Rated residual operating current
RCBO
RCCB
Release for work
Residual current
Residual current device
Restricted approach boundary
Risk assessment
S
Short circuit
Skilled person
Step voltage
Stored electrical energy
Switch-disconnector
T
Tagout
Touch voltage
TT system
Two-pole voltage tester
Type B RCD
V
Ventricular fibrillation
W
Working distance
About this lesson