Alternating Current Basics

Learn how the alternating voltage from the grid, a generator or an inverter is described and what it does in real circuits. You will convert between period and frequency and between peak and rms values, see why inductors and capacitors make the current lag or lead, and calculate impedance, current and phase angle in series and parallel circuits. You will then work with active, reactive and apparent power, correct a low power factor with capacitors, and use line and phase values, star and delta connections and three-phase power in buildings, vehicles and aircraft.

IntermediateLesson 4 of 7 in Electrical Principles for Technicians Course

What you will learn

  1. Explain how a sine-wave voltage is produced, read its period and frequency, and convert between the peak, peak-to-peak, average and rms values that describe its size.
    • Read a sine wave: cycle, period and frequency
      Describe how a rotating generator produces a sine wave, and use period, frequency and instantaneous values to read AC waveforms on paper and on an oscilloscope.
    • Use peak, peak-to-peak, average and rms values
      Convert between the values that describe the size of a sine wave, explain what an rms value means, and know which value a meter shows and which value a component must withstand.
  2. Describe the phase relationship between voltage and current in resistors, inductors and capacitors, and calculate inductive and capacitive reactance at any frequency.
    • Describe phase difference and resistive circuits
      Describe lead and lag between two sine waves of the same frequency, draw simple phasor diagrams, and apply Ohm's law and the power formula to purely resistive AC circuits.
    • Calculate inductive reactance and describe current lag
      Explain why an inductor opposes alternating current, calculate its reactance from frequency and inductance, and describe how its current lags the voltage.
    • Calculate capacitive reactance and describe current lead
      Explain how a capacitor carries alternating current, calculate its reactance from frequency and capacitance, and describe how its current leads the voltage.
  3. Combine resistance and reactance into impedance in series and parallel circuits, and use right-triangle methods to find currents, voltages and phase angles and how they change with frequency.
    • Analyze series RL and RC circuits
      Use the impedance and voltage triangles to find impedance, current, component voltages and phase angle in series circuits with resistance and one kind of reactance.
    • Analyze series RLC circuits and resonance
      Combine inductive and capacitive reactance in one series circuit, decide whether it behaves inductively or capacitively, and describe series resonance.
    • Analyze parallel AC circuits
      Find branch currents, the total current and the phase angle when resistors, inductors, capacitors and real loads are connected in parallel across one supply.
  4. Distinguish active, reactive and apparent power, explain what the power factor means for a load and for the supply, and size a capacitor that corrects a low power factor.
    • Use the power triangle: active, reactive and apparent power
      Calculate active, reactive and apparent power in single-phase circuits and relate them with the power triangle.
    • Explain the power factor and its effects
      Define the power factor, recognize lagging and leading loads, measure the power factor, and explain why a low power factor costs current, losses and money.
    • Correct a low power factor with capacitors
      Explain how parallel capacitors improve a lagging power factor, calculate the capacitor's reactive power and capacitance, and describe practical correction methods and their hazards.
  5. Describe common single-phase and three-phase supply systems, convert between line and phase values in star and delta, calculate three-phase power, and explain why loads are balanced and how equipment uses a three-phase supply.
    • Describe single-phase supply systems
      Identify the conductors and voltages of common single-phase supplies and calculate the current of single-phase loads.
    • Relate line and phase values in star and delta
      Describe how three-phase voltages are produced and convert between line and phase voltages and currents in star (wye) and delta connections.
    • Calculate three-phase power and balance the load
      Calculate the power and line current of balanced three-phase loads, find the neutral current of unbalanced loads, and explain why loads are spread evenly over the phases.
    • Explain how equipment uses a three-phase supply
      Describe how three-phase currents create a rotating magnetic field, connect a motor in star or delta from its nameplate, and recognize three-phase AC in buildings, vehicles and aircraft.

Alternating Current study guide

5 chapters

1

Read and measure an AC waveform

An AC waveform tells you both how quickly a supply changes and how large its voltage becomes. Reading its time scale leads to frequency; reading its vertical scale leads to peak and rms values. These measurements answer different equipment questions: the heating a load produces, the voltage its insulation must withstand, and the frequency its magnetic parts will experience. A sine wave gives a clear starting point for all three.

1.1 Cycles, time and frequency

An alternating voltage reverses polarity, and an alternating current reverses direction. A sine wave rises smoothly to a positive peak, falls through zero to a negative peak, and returns to its starting point. That complete pattern is one cycle.

From rotation to a waveform

A coil turning at constant speed in a uniform magnetic field has an induced voltage that follows the sine of its angle. In a simple two-pole generator, one turn gives one cycle. One cycle contains 360 electrical degrees. Starting at an upward zero crossing, the positive peak is at 90°, the next zero crossing at 180°, and the negative peak at 270°.

The period, T, is the time for one cycle. The frequency, f, counts cycles per second in hertz (Hz):

f=1T,T=1f

Convert milliseconds to seconds before taking the reciprocal. At 50 Hz, the period is 0.020 s, or 20 ms. At 60 Hz it is about 16.7 ms; at 400 Hz it is 2.5 ms. A faster repetition shortens the wave horizontally. It does not make the peak taller.

Read the scales

On an oscilloscope, the horizontal scale is time per division. If a full cycle covers four divisions at 5 ms/div, its period is 4×5=20 ms. Convert to 0.020 s and calculate f=1/0.020=50 Hz. Count between matching points, such as two successive upward zero crossings. Adjacent zero crossings are only half a cycle apart.

The vertical scale is volts per division. A trace extending 6.5 divisions from its lowest to highest point at 100 V/div spans 650 V peak to peak. Its peak measured from the zero line is 325 V.

Measurement safety: A standard bench oscilloscope's probe ground is connected to protective earth. Never clip it to a line conductor or disconnect the oscilloscope's protective earth. Use a correctly rated differential probe, rated isolated inputs, or a reduced-voltage transformer copy of the waveform for this measurement.

Find a value at one moment

The instantaneous voltage depends on position within the cycle:

v=Vpksin⁡θ,θ=360∘ft

Measure time from an upward zero crossing and use degree mode. For a 325 V peak at 50 Hz, 2.5 ms corresponds to 360∘×50×0.0025=45∘. The voltage is therefore 325sin⁡45∘≈230 V. This is one moment's value; it is not a new peak or a new supply rating.

Match frequency to the source

Generator speed and pole count set the frequency:

f=pn60

Here p is the number of pole pairs and n is speed in rpm. Two poles mean one pair: 3000 rpm gives 50 Hz. Four poles mean two pairs, so 1500 rpm gives the same 50 Hz. Counting poles as pairs would double the answer.

Many grids operate at 50 Hz; North American grids generally use 60 Hz. Japan uses 50 Hz in the east and 60 Hz in the west. Aircraft commonly use 400 Hz, which allows smaller magnetic equipment. The source frequency is an equipment characteristic to check alongside voltage.

Key Takeaways

  • A full cycle runs between matching points on successive repetitions.
  • Use seconds in f=1/T; 20 ms is 0.020 s.
  • Amplitude and frequency describe different features of a wave.
  • Generator frequency depends on speed and the number of pole pairs.
  • Instantaneous voltage follows v=Vpksin⁡θ from an upward zero crossing.

1.2 Peak voltage and effective voltage

An AC voltage has several useful size measurements. The right one depends on whether you are reading a trace, calculating heating, or checking a component's voltage stress. Supply voltage and current ratings normally use rms values.

Choose the measurement
ValueWhat it measuresSymmetrical sine wave
PeakZero to the highest positive valueVpk
Peak to peakNegative peak to positive peakVpp=2Vpk
Full-cycle averageSigned average over a complete cycleZero
Half-cycle averageAverage over the positive half cycle2Vpk/π≈0.637Vpk
rmsEquivalent DC heating valueVrms=Vpk/2

Root-mean-square means the DC voltage that would produce the same average heating in the same resistor. The positive and negative halves both heat the resistor: reversing both voltage and current keeps their product positive. A full-cycle average of zero therefore does not mean zero heating.

For a sine wave:

Vpk=2Vrms,Vrms=Vpk2

The same relationships apply to sinusoidal current. Peak is larger than rms. Use that size check to catch a reversed conversion.

Work from a supply rating

A 230 V supply is 230 V rms. Its peak is 2302≈325 V and its peak-to-peak value is about 650 V. The half-cycle average is 325×0.637≈207 V. A 120 V rms sine wave reaches about 170 V peak; a 115 V aircraft supply reaches about 163 V.

For a 52.9 Ω heater on 230 V rms:

I=23052.9≈4.35 A P=230252.9=1000 W

Its peak current is about 4.352=6.15 A. The heater produces the same average heat as it would on 230 V DC. Use rms current for the heating of conductors and fuses. Insulation and electronic components also have to withstand waveform peaks, supply variation and surges; a 230 V rms label does not limit instantaneous voltage to 230 V.

Understand the meter

An average-responding AC meter measures the rectified average and scales it by about 1.11 to display rms for a sine wave. That conversion is built around the sine-wave shape. Currents drawn by LED drivers, switch-mode supplies and variable-speed drives can be distorted, so they need a true-rms meter with suitable ratings and bandwidth.

A true-rms instrument determines the heating-related value without assuming a sine-wave shape. Do not apply the sine-wave peak factor to every waveform: a symmetrical square wave has rms equal to its peak magnitude. A meter's AC reading also does not replace a waveform display when you need the actual shape or peak.

The half-cycle average is useful when examining rectification. It describes the average of the rectified sine wave, while rms describes heating. Keeping those purposes separate prevents a rectifier average from being substituted into an AC power calculation.

Key Takeaways

  • rms gives the DC-equivalent heating effect in a resistor.
  • For a sine wave, peak is rms multiplied by 2.
  • Peak to peak is twice the peak for a wave symmetrical about zero.
  • A zero signed average does not imply zero power.
  • Average-responding meters rely on a sine-wave calibration.
  • Use true-rms measurement for distorted waveforms within the instrument’s ratings.
2

Predict current in resistors, coils and capacitors

A resistor turns electrical energy into heat. A coil stores energy in a magnetic field, while a capacitor stores it in an electric field. These different actions explain why voltage and current can reach their peaks at different times. You will describe that timing as lead or lag, calculate the opposition called reactance, and predict how a change in frequency affects a component before combining components into a circuit.

2.1 Phase difference and resistive loads

Two sine waves can have the same frequency and still reach their peaks at different times. Their phase difference expresses that timing shift as part of a cycle. The wave reaching a matching point first leads; the later wave lags.

Turn a time shift into an angle

One complete period represents 360°. The relationship is:

Δt=φ360∘T

At 50 Hz, one period is 20 ms. A current lag of 30° corresponds to Δt=(30/360)×20≈1.67 ms. At 60 Hz, the same angle corresponds to about 1.39 ms because the whole cycle is shorter. Compare waves of the same frequency when describing a fixed phase difference.

An oscilloscope trace gives the direction of the shift as well as its size. If the voltage's positive peak appears before the current's positive peak, voltage leads and current lags. Saying only “30°” leaves out which quantity comes first.

Draw a phase relationship

A phasor is an arrow representing a sinusoidal quantity. Its length shows size, usually rms, and its angle shows phase. Imagine the arrows rotating counterclockwise together. An arrow further counterclockwise leads.

Choose a shared reference. In a series circuit, the same current passes through every component, so draw current along the horizontal zero-degree line. In a parallel circuit, all branches share voltage, so voltage is the reference. These drawings let you compare timing without drawing complete waves.

Arrows along the same direction add by ordinary arithmetic. Arrows at right angles form a right triangle: their resultant length follows the Pythagorean theorem. An arrow's length is a magnitude; its angle is essential when combining it with another quantity.

Calculate a heater's current and power

For a pure resistor, current and voltage are in phase. They pass through zero together and have their positive and negative peaks together. With rms values, Ohm's law applies:

I=VR

A 46 Ω heater on 230 V takes I=230/46=5 A. Its average power is P=VI=230×5=1150 W. Series resistor voltages add normally, and parallel resistor currents add normally, because the quantities being added are in phase.

Instantaneous power is p=vi. During the negative half cycle, both voltage and current are negative, so their product is positive. Resistor power pulses from zero to 2VrmsIrms at twice the supply frequency. This heater's instantaneous power reaches 2300 W, while its average remains 1150 W.

Know when DC addition stops working

The resistance of ordinary heaters and wiring at 50 or 60 Hz is practically the DC value. At higher frequencies, skin effect pushes current toward a conductor's surface and raises its effective resistance; thick conductors can show this at 400 Hz.

Inductors and capacitors introduce phase shifts. Their out-of-phase voltage or current magnitudes cannot simply be added as if they peaked together. Two quantities that really are in phase still add arithmetically, even in an AC circuit.

Key Takeaways

  • Lead and lag say which same-frequency wave reaches a matching point first.
  • Phase angle is the time shift expressed as a fraction of 360°.
  • A pure resistor has current and voltage in phase.
  • Use the shared current as the series reference and shared voltage as the parallel reference.
  • Combine out-of-phase quantities with their directions as well as their magnitudes.

2.2 Coils and inductive reactance

A coil resists a change in current. As its current changes, so does its magnetic field. That changing field induces a voltage opposing the change. In an AC circuit this action produces inductive reactance, measured in ohms.

Calculate the opposition

Inductive reactance is:

XL=2πfL

Use frequency in hertz and inductance in henries. A 100 mH coil has L=0.1 H. At 50 Hz:

XL=2π×50×0.1≈31.4 Ω

At 60 Hz the same coil has about 37.7 Ω reactance, and at 400 Hz about 251 Ω. Doubling frequency doubles reactance. Increasing inductance also increases reactance.

For an ideal coil, I=V/XL. On 230 V at 50 Hz, the 0.1 H coil carries about 230/31.4=7.32 A. At 400 Hz on the same voltage it carries about 0.915 A. Voltage is unchanged; the faster change in current makes the inductive opposition larger.

Explain the lag

In an ideal inductor, current lags voltage by 90°, or one quarter cycle. At 50 Hz that is 5 ms. The voltage is greatest when the current is changing fastest, not when the current has reached its peak. At a current peak the slope is zero, so the ideal inductor's voltage is zero.

The memory aid ELI places voltage E before current I around inductance L. The useful meaning is “voltage leads current in an inductor.” Real motor and transformer windings also have resistance and losses. Their current usually lags by less than 90°.

Distinguish reactance from resistance

An ohmmeter uses DC and reports winding resistance. It does not report the coil's AC reactance. A coil reading 12 Ω on an ohmmeter may have AC impedance above 100 Ω. From AC voltage and current you obtain total impedance magnitude:

Z=VI

For a series resistance-inductance model, use the known resistance to separate the inductive part:

XL=Z2−R2

At steady DC, frequency is zero and inductive reactance is zero. Current is then limited by winding resistance. An AC contactor coil with 15 Ω resistance connected to 230 V DC would draw about 15.3 A once steady, even if its normal AC current were only about 0.2 A. The AC and DC voltage ratings of a coil are therefore not interchangeable.

Follow the stored energy

An ideal inductor stores energy in its magnetic field and gives it back. Its average power is zero, although current flows. A real coil heats because winding resistance and core losses convert some input energy into heat.

Adding turns or using an iron core generally increases inductance. Coils appear in relays, contactors, motors, transformers and chokes. A choke offers relatively little opposition to steady DC and stronger opposition to high-frequency AC. That frequency dependence helps filters reduce electrical interference.

Key Takeaways

  • An inductor opposes changes in current through self-induction.
  • Calculate XL=2πfL using henries.
  • Ideal inductive current lags voltage by 90°.
  • An ohmmeter measures winding resistance, not AC reactance.
  • An ideal inductor returns stored energy; real coils also have losses.
  • At steady DC the coil’s winding resistance limits current.

2.3 Capacitors and capacitive reactance

A capacitor has two conductors separated by an insulating dielectric. Changing the voltage moves charge onto one plate and off the other. Repeated charging and discharging produces alternating current in the connecting circuit without charge crossing the ideal dielectric.

Use farads in the calculation

Capacitance measures how much charge is stored for a given voltage. Its unit is the farad (F), but practical values commonly use microfarads, nanofarads or picofarads. One microfarad is 10−6 F; one millifarad is 10−3 F. Confusing the two changes a calculation by a factor of 1000.

Capacitive reactance is:

XC=12πfC

For 10 µF at 50 Hz, enter C=10×10−6 F:

XC=12π×50×10×10−6≈318 Ω

On 230 V the ideal capacitor current is I=230/318≈0.723 A. At 60 Hz its reactance is about 265 Ω, and at 400 Hz about 39.8 Ω. Frequency and capacitance are in the denominator: doubling either one halves the reactance. At fixed voltage, that doubles the current.

Explain why current leads

In an ideal capacitor, current leads voltage by 90°. Current is greatest at a voltage zero crossing because the voltage is changing fastest there. At the voltage peak the change momentarily stops and the current is zero.

The memory aid ICE puts current I before voltage E around capacitance C. An ideal capacitor stores energy in an electric field and returns it each quarter cycle. Its average power is zero. Its leading current can oppose the lagging current of an inductive load at the supply connection.

ComponentEffect of raising frequencyIdeal current timing
InductorReactance increases90° behind voltage
CapacitorReactance decreases90° ahead of voltage
Apply its frequency behavior

After a capacitor finishes charging from DC, no steady current flows through the ideal capacitor. As frequency approaches zero, capacitive reactance grows very large. Higher-frequency AC passes more easily. In a loudspeaker crossover, a capacitor in series with a tweeter holds back low frequencies. A series inductor does the opposite for a woofer.

Larger plate area increases capacitance; greater plate spacing reduces it. A dielectric with higher permittivity also increases capacitance. In a capacitive aircraft fuel probe, rising fuel replaces air between the conductors. The change in dielectric changes capacitance, which the gauging system measures.

Respect stored charge and voltage ratings

A capacitor can retain a dangerous charge after disconnection. Follow the equipment's discharge instructions, wait the specified time and verify zero voltage before touching its terminals. Do not assume that a discharge resistor is fitted or that it has worked.

A capacitor's rating must match its duty as well as the voltage across it. Motor-run capacitors used with a 230 V supply commonly carry an AC rating such as 400 V or 450 V. A voltage value without its AC or DC duty is not enough to identify a suitable replacement.

Key Takeaways

  • Capacitor current comes from charging and discharging as voltage changes.
  • Use XC=1/(2πfC) with capacitance in farads.
  • Increasing frequency or capacitance lowers capacitive reactance.
  • Ideal capacitive current leads voltage by 90°.
  • A charged ideal capacitor blocks steady DC.
  • Capacitance depends on plate area, spacing and dielectric.
  • Stored charge can remain after the supply is removed.
3

Solve mixed AC circuits with triangles

Mixed circuits need both size and timing. In series circuits you combine component voltages; in parallel circuits you combine branch currents. Right triangles give the total when resistive and reactive parts are 90° apart. You will use that method to calculate impedance and phase angle, then examine what happens when inductive and capacitive effects cancel at resonance. Component readings can exceed a supply reading without breaking the circuit laws.

3.1 Impedance in series RL and RC circuits

The same current passes through every part of a series circuit. A resistor's voltage is in phase with that current. An ideal inductor's voltage is 90° ahead of it; an ideal capacitor's voltage is 90° behind it. The supply voltage combines these timed contributions.

Build the impedance triangle

For series resistance and one kind of reactance:

Z=R2+X2,I=VZ

Impedance magnitude Z is the total AC opposition in ohms. Draw resistance horizontally, reactance vertically, and impedance as the hypotenuse. The triangle also gives:

tan⁡φ=XR,cos⁡φ=RZ

Use the magnitude of reactance for the angle size and state lead or lag from the component. An RL circuit gives lagging current; an RC circuit gives leading current. In a signed drawing inductive reactance points up and capacitive reactance points down.

Work an RL circuit

Connect 30 Ω resistance and 40 Ω inductive reactance in series on 230 V:

  1. Impedance: Z=302+402=50 Ω.
  2. Current: I=230/50=4.6 A.
  3. Resistor voltage: VR=IR=4.6×30=138 V.
  4. Inductor voltage: VL=IXL=4.6×40=184 V.
  5. Phase angle: φ=tan⁡−1(40/30)≈53.1∘, current lagging.

The power factor is cos⁡φ=30/50=0.6. Check the supply with 1382+1842=230 V. Adding the readings as 138 + 184 would give 322 V, but those two voltages reach their peaks at different times. Likewise, adding 30 + 40 is not the impedance calculation.

Work an RC circuit

For 120 Ω resistance and 50 Ω capacitive reactance on 230 V:

Z=1202+502=130 Ω

Current is 230/130≈1.77 A. Keeping the unrounded current gives about 212 V across the resistor and 88.5 V across the capacitor. The phase angle is tan⁡−1(50/120)≈22.6∘ leading, with power factor 120/130≈0.923. The impedance triangle has the same length rules as RL, but the current timing reverses.

Learn about a real coil from measurements

A coil has 12 Ω DC resistance and draws 2.0 A at 230 V, 50 Hz. First find Z=230/2.0=115 Ω. For its series RL model:

XL=1152−122≈114.4 Ω L=114.42π×50≈0.364 H

Voltage divided by current gives impedance, not reactance alone.

Frequency changes the triangle. With 30 Ω and 0.1 H on 230 V, raising frequency from 50 to 400 Hz raises reactance from about 31.4 to 251 Ω. Impedance rises from about 43.4 to 253 Ω and current falls from about 5.29 to 0.909 A. A series RC circuit responds in the opposite direction: increasing frequency lowers its capacitive reactance and increases its current toward the resistance-limited value.

Key Takeaways

  • Find series impedance with a right triangle, not R+X.
  • Calculate the common current before component voltage drops.
  • Component voltages combine according to their phase relationships.
  • RL current lags; RC current leads.
  • AC voltage and current measurements give impedance magnitude.
  • Frequency changes reactance, impedance and phase angle.

3.2 Series RLC circuits and resonance

A series RLC circuit contains resistance, inductance and capacitance in the same current path. The inductor and capacitor voltages point in opposite directions on the voltage diagram. Their effects subtract before the reactive part combines with resistance.

Find the net reactance first

Use:

X=XL−XC,Z=R2+(XL−XC)2

If inductive reactance is larger, current lags. If capacitive reactance is larger, current leads. Equal reactances cancel at the supply, giving zero net phase angle. The resistor voltage remains in phase with current in each case.

For 40 Ω resistance, 100 Ω inductive reactance and 70 Ω capacitive reactance on 230 V:

  1. Net reactance: X=100−70=30 Ω, inductive.
  2. Impedance: Z=402+302=50 Ω.
  3. Current: I=230/50=4.6 A.
  4. Angle: φ=tan⁡−1(30/40)≈36.9∘ lagging.

The power factor is 40/50=0.8. Adding the two reactances would miss their opposite phase directions and greatly overstate impedance.

Check each component voltage

The common current gives VR=184 V, VL=460 V and VC=322 V. A 460 V component reading on a 230 V supply can be correct. The reactive voltages oppose each other, leaving 460−322=138 V. The supply is:

V=1842+1382=230 V

Each component must withstand the voltage across itself.

Find the resonant frequency

Series resonance occurs when XL=XC. Solving the two reactance formulas gives:

f0=12πLC

Use henries and farads. With 0.1 H and 10 µF, the product is 0.1×10×10−6=10−6. Its square root is 0.001, so f0=1/(2π×0.001)≈159 Hz.

At resonance, Z=R and I=V/R. For fixed supply voltage and resistance this is the largest current. Supply current is in phase with supply voltage and the power factor is 1. The inductor and capacitor can each have a large voltage, even though their combined voltage is zero.

Predict which side of resonance you are on

As frequency rises, inductive reactance rises and capacitive reactance falls. Below resonance, capacitive reactance wins and current leads. Above resonance, inductive reactance wins and current lags. At 50 Hz the 0.1 H and 10 µF combination has about 31.4 Ω inductive reactance and 318 Ω capacitive reactance, so it is capacitive.

Tuned circuits and filters use resonance to select a frequency. Accidental resonance between network inductance and capacitors can also magnify currents and voltages.

Key Takeaways

  • Subtract XC from XL before combining reactance with resistance.
  • The larger reactance determines whether current leads or lags.
  • Component voltages can exceed supply voltage.
  • At series resonance, impedance is minimum and current is maximum for fixed voltage and resistance.
  • Below resonance the circuit is capacitive; above it the circuit is inductive.

3.3 Current in parallel AC branches

Every parallel branch has the same supply voltage. Use that voltage as the phase reference and find the branch currents first. The branch current readings may add to much more than the supply current because they reach their peaks at different times.

Separate current by timing

For ideal resistor, inductor and capacitor branches:

IR=VR,IL=VXL,IC=VXC

The resistor current is in phase with voltage. Inductor current lags by 90°; capacitor current leads by 90°. Their reactive currents oppose, leaving a net reactive magnitude based on IL−IC. Combine it with the resistive current:

I=IR2+(IL−IC)2 Z=VI,tan⁡φ=IL−ICIR

A positive inductive remainder means lagging supply current. A capacitive remainder means leading supply current. The power factor for these sinusoidal currents is IR/I.

Work three branches

On 230 V, a 46 Ω resistor takes 5 A, a 23 Ω inductive reactance takes 10 A, and a 46 Ω capacitive reactance takes 5 A. The net reactive current is 10−5=5 A lagging. Thus:

I=52+52≈7.07 A Z=230/7.07≈32.5 Ω

The phase angle is 45° lagging and power factor is about 0.707. A supply clamp meter reads about 7.07 A, not the arithmetic total of 20 A. The opposing reactive currents partly circulate between branches.

With the capacitor removed, the resistor and inductor still take 5 A and 10 A. Supply current becomes 52+102≈11.2 A. Adding the capacitor reduced supply current while leaving both original branch currents unchanged at the same voltage.

Combine a real load with a heater

A motor draws 10 A at power factor 0.8 lagging. Its in-phase part is 10×0.8=8 A. Its reactive part is 101−0.82=6 A lagging. A parallel heater adds 5 A in phase, giving 13 A in phase and 6 A reactive:

I=132+62≈14.3 A

The combined power factor is about 13/14.3=0.91 lagging. Adding the motor and heater magnitudes as 15 A would treat their currents as if they had the same timing.

Recognize parallel resonance

When ideal inductive and capacitive branch currents are equal, they cancel at the supply. The supply then carries only the resistor current, in phase with voltage. In a parallel ideal LC pair, the net reactive supply current is zero at resonance, even though nonzero currents flow in its branches. Real losses require some supply current.

The series impedance formula does not apply directly to separate parallel branches. A 46 Ω resistor in parallel with 23 Ω inductive reactance on 230 V has currents of 5 A and 10 A, total about 11.2 A, and impedance about 20.6 Ω. Calculate branch currents before drawing the current triangle.

Key Takeaways

  • Parallel branches share voltage; calculate their currents separately.
  • Inductive and capacitive branch currents subtract.
  • In-phase and net reactive currents combine at right angles.
  • Split a real load current into in-phase and reactive components before combining loads.
  • Parallel cancellation can leave substantial current inside the branches.
  • Adding a parallel capacitor can lower supply current without lowering motor current.
4

Calculate power and reduce supply current

An AC load can draw current both to convert energy and to exchange stored energy with the supply. Active, reactive and apparent power describe those different demands. Their triangle explains power factor and why a motor can burden a supply more than its wattage suggests. You will calculate the three quantities, use measurements to judge power factor, and find how much parallel capacitance is needed to reduce a lagging reactive demand.

4.1 Watts, var and volt-amperes

A heater and a motor drawing the same current at the same voltage need not convert energy at the same rate. The motor's phase shift changes the average of voltage times current. Three power quantities separate energy conversion from current demand.

Name the three quantities
QuantityMeaningSinusoidal single-phase formula
Active power, WAverage energy conversion into heat, light or workP=VIcos⁡φ
Reactive power, varEnergy exchange with magnetic or electric fieldsQ=VIsin⁡φ
Apparent power, VAProduct of rms voltage and rms currentS=VI

Use rms voltage and current throughout. Energy meters record active energy in kilowatt-hours. A kilowatt-hour is energy, whereas a kilowatt is power. Transformers and generators have kVA ratings because their voltage and current burdens matter even when the load's power factor is low.

Reactive power describes a repeated exchange. An ideal inductor stores energy in its magnetic field; an ideal capacitor stores energy in its electric field. Each returns stored energy to the circuit, so its average active power is zero. The current carrying that exchange still heats resistance in real supply cables.

Build the power triangle

For sinusoidal voltage and current, draw active power horizontally and reactive power vertically. Apparent power is the hypotenuse:

S2=P2+Q2 P=Scos⁡φ,Q=Ssin⁡φ

Inductive reactive power is taken as positive and capacitive reactive power as negative. For combined loads, active powers add, while inductive and capacitive reactive powers oppose: Qtotal=QL−QC. Calculate apparent power from the resulting totals, not by adding separate apparent powers blindly.

Work a motor's input power

A motor takes 10 A from 230 V at power factor 0.8 lagging. First calculate S=230×10=2300 VA. Then:

P=2300×0.8=1840 W

Since sin⁡φ=1−0.82=0.6:

Q=2300×0.6=1380 var

The check is 18402+13802=2300 VA. Multiplying voltage by current alone gives apparent power, not this motor's active input. Shaft output would also require the motor's efficiency.

Connect power to circuit components

In a series circuit, the resistance converts active power and reactance accounts for reactive power:

P=I2R,Q=I2X

With 30 Ω resistance, 40 Ω inductive reactance and 4.6 A, active power is about 635 W and reactive power about 846 var. Apparent power is 230×4.6=1058 VA. Multiplying every side of the impedance triangle by current squared produces the power triangle.

Instantaneous power is p=vi. It becomes negative during parts of a cycle when voltage and current have opposite signs: energy then returns toward the supply. A real inductive load still has positive average active power. Do not describe its entire input as lost heat simply because some of its current is reactive.

Key Takeaways

  • Active power measures average energy conversion in watts.
  • Reactive power describes energy exchange and is measured in var.
  • Apparent power is rms voltage times rms current, in VA.
  • For sinusoidal quantities, S2=P2+Q2.
  • Add active powers and signed reactive powers before finding total apparent power.
  • Electrical motor input and shaft output are different power measurements.

4.2 Power factor and supply losses

Power factor tells you how much active power a load takes for its apparent power. A low value means more supply current for the same active power and voltage. That matters to cables and transformers even when the load is doing exactly the same useful work.

Define it before calculating an angle
PF=PS

For a consuming load, power factor lies between 0 and 1. With sinusoidal voltage and current it is cos⁡φ. Describe inductive loads as lagging and capacitive loads as leading; the number alone does not identify that timing.

Resistive heaters have power factor close to 1. Induction motors and transformers draw lagging magnetizing current. An induction motor may have power factor around 0.85 under full load but below 0.5 unloaded. Its active demand falls with mechanical load while its magnetic field still needs current.

Power factor is different from efficiency. Efficiency compares useful output with active input. Power factor compares active input with apparent input. A low-power-factor motor is not converting all of its reactive power into waste heat.

Calculate the current penalty

For a sinusoidal single-phase load:

I=PVcos⁡φ

A 10 kW load on 230 V takes about 43.5 A at power factor 1. At 0.7 it takes about 62.1 A. The same active power now needs 1/0.7≈1.43 times the current.

Cable heating follows Ploss=I2R. With the same cable resistance, the loss ratio is:

(10.7)2≈2.04

That is about twice the cable loss, not 43% more. Increased current also raises voltage drop and occupies more of a transformer's current capacity. Some commercial and industrial tariffs charge for reactive energy or low power factor, but the electrical current penalty exists regardless of the billing arrangement.

Use measured watts and rms values

A load on 230 V takes 5.2 A and a wattmeter reads 850 W:

S=230×5.2=1196 VA PF=850/1196≈0.71

For sinusoidal current, the angle is cos⁡−1(850/1196)≈44.7∘. Wattage and current magnitude alone do not tell you whether that angle is leading or lagging; phase measurement or knowledge of the load supplies the direction.

Recognize distorted current

Rectifiers, LED drivers and variable-speed drives may draw current in pulses. True power factor remains P/(VrmsIrms), but the cosine of the angle between fundamental-frequency voltage and current is only the displacement power factor. With a sinusoidal supply, current distortion can reduce true power factor even when the fundamental current is nearly in phase.

Use a true-rms power analyzer to assess such a load. A capacitor addresses lagging reactive current; it does not remove the distortion by itself. Applying cos⁡−1(PF) to a distorted waveform as if it described one simple time shift would hide the cause of the extra current.

Key Takeaways

  • Power factor is active power divided by apparent power.
  • With sinusoidal voltage and current, power factor equals cos⁡φ.
  • Lower power factor needs more current at fixed active power and voltage.
  • Supply conductor losses increase with current squared.
  • Power factor and efficiency compare different quantities.
  • Distorted current requires true-power-factor measurement.

4.3 Parallel capacitors for power-factor correction

An inductive load needs lagging reactive current. A capacitor connected in parallel supplies leading reactive current at the same location. Those reactive contributions partly cancel at the supply, lowering the current in upstream cables.

Keep the motor and supply separate

At fixed voltage and mechanical load, correction does not change the motor's own current, active power or reactive demand. It changes what the supply must provide to the motor-capacitor combination. The motor's active power continues to come from the supply; some of the reactive exchange now occurs locally.

The correction calculation uses the power triangle before and after compensation:

QC=P(tan⁡φ1−tan⁡φ2)

The existing power factor determines φ1, and the target determines φ2. Use active electrical input power for P. Keep watts with var, or kilowatts with kvar.

Calculate the required reactive power

Correct a 10 kW, 230 V, 50 Hz load from 0.7 to 0.95 lagging. The angle calculations give:

tan⁡(cos⁡−10.7)≈1.0202 tan⁡(cos⁡−10.95)≈0.3287

The original reactive demand is about 10.2 kvar and the desired remainder is about 3.29 kvar. Subtracting with unrounded values gives:

QC=10000(1.020204−0.328684)≈6915 var

The capacitor therefore supplies about 6.92 kvar. Using the entire original 10.2 kvar would target unity power factor instead of the specified 0.95.

Convert var into capacitance

For a single-phase capacitor across rms voltage V:

QC=2πfCV2,C=QC2πfV2

Using unrounded reactive power:

C≈6915.22π×50×2302≈0.0004161 F=416 μF

The original supply current was about 62.1 A. After correction it is 10000/(230×0.95)≈45.8 A. Active power stays at 10 kW in this calculation; lower upstream losses are a separate benefit.

Choose correction to follow the load

Individual correction switches a capacitor with one motor. Group correction serves several loads together. Central correction uses a controller to switch capacitor-bank steps as the total demand changes. Three-phase loads use appropriately connected three-phase banks.

Targets around 0.95 leave room for load changes. If too much capacitance remains connected at light load, the supply becomes leading and current can rise again. Moving from 0.95 to exactly 1 saves relatively little current and requires closer control.

Distorted currents introduce another concern: capacitors can resonate with supply inductance and amplify harmonic current. Detuned banks include series reactors to manage that risk. The simple sizing formula describes the reactive requirement; suitable equipment also depends on voltage duty, switching conditions and distortion.

Key Takeaways

  • Connect correction capacitors in parallel with an inductive load.
  • Calculate the required reduction in reactive power from both power-factor angles.
  • For a single-phase capacitor, C=QC/(2πfV2).
  • Correction lowers upstream current without changing the motor’s active power at fixed conditions.
  • Excess capacitance can produce a leading power factor.
  • Automatic steps follow changing demand; detuned banks address resonance risk.
5

Use single-phase and three-phase supply values

Supply labels describe voltages between particular conductors, so a voltage number alone does not tell you what a winding receives. Single-phase, star and delta connections give different relationships between line and phase values. You will use those relationships to calculate power, judge balance and read motor nameplates. The same principles explain a building supply, an electric vehicle charger, and a 400 Hz aircraft system.

5.1 Single-phase supplies and conductors

A single-phase load receives one alternating voltage between two current-carrying conductors. These can be line and neutral, or two lines. A protective earth conductor serves protection and is not the intended load-current return.

Identify conductor functions

The line conductor is also called phase or, in North America, hot. The neutral is connected to the source's neutral point and commonly bonded to earth at the source or service arrangement. It carries load current. Protective earth, also called equipment ground, provides a fault-current path to help protective equipment disconnect a fault. Equipment can also produce small normal leakage currents in protective conductors.

Neutral is normally near earth potential in an earth-referenced supply, but load-related voltage drop or a broken connection can put it at a dangerous voltage. Confirm conductor functions and prove the circuit dead before contact; a color or nominal voltage is not proof of safety.

Compare common supplies
SupplySource arrangementVoltage used by a load
230 V, 50 HzOne line and neutral of a 230/400 V network230 V line to neutral
120/240 V, 60 HzOne winding with a grounded center tap120 V from either end to neutral, 240 V end to end
230 V line to lineTwo lines of a 3 × 230 V network230 V between lines

The 120/240 V arrangement is split-phase. The two hot-to-neutral voltages are 180° apart, so their end-to-end voltage is 240 V. It is a single-phase source from one transformer winding. Two hot conductors do not make it a three-phase supply. Receptacles commonly use 120 V; larger loads such as ranges and water heaters may use 240 V.

These are nominal rms voltages. Actual values vary; many European public supplies use a normal service range around 230 V, commonly described as ±10%. A circuit calculation uses the stated voltage, while equipment selection also checks the allowed operating range.

Calculate load current

For a sinusoidal single-phase load:

I=PVcos⁡φ

A resistor has power factor 1. A 3 kW kettle on 230 V therefore takes 3000/230≈13.0 A. A 1.5 kW kettle on 120 V takes 1500/120=12.5 A. At the same active power and power factor, lowering voltage raises current. For a motor, include power factor when converting active electrical input power into current.

Read colors as identification clues

In common European wiring, single-phase line is brown, neutral blue, and protective earth green-and-yellow; black and gray also identify lines in three-phase wiring. In US wiring, black and red are common hot colors, white or gray identify neutral, and green or bare copper identify equipment ground. Hot colors are not a universal fixed phase sequence. Older installations and some equipment use other conventions.

Single-phase power pulsates at twice supply frequency. A single-phase induction motor's main winding produces a pulsating magnetic field; an auxiliary winding with phase shift or shaded poles provides starting torque. A three-phase supply instead supports a rotating field directly, which suits larger motors and heavy loads.

Key Takeaways

  • A single-phase load can be connected line to neutral or line to line.
  • Neutral carries load current; protective earth is not the intended load return.
  • Split-phase 120/240 V comes from a center-tapped single-phase winding.
  • Use electrical input power and power factor when calculating motor supply current.
  • Conductor colors depend on the wiring convention and do not prove a circuit safe.

5.2 Star, delta, line and phase values

A three-phase source produces three equal-frequency voltages spaced by 120 electrical degrees. The order of their peaks is the phase sequence, often L1–L2–L3. At 50 Hz the time spacing is one third of 20 ms, about 6.67 ms.

Separate line from phase

A line voltage is measured between two line conductors. A phase voltage is across one source winding or load element. Line current flows in a line conductor; phase current flows through one winding or element. First identify the connection, then decide which quantity a number describes.

ConnectionVoltage relationshipCurrent relationship
Star, or wye (Y)VL=3Vph for balanced phase voltagesIL=Iph
DeltaVL=VphIL=3Iph for balanced branch currents

In star, one end of each winding joins at a star point. It can provide a neutral connection. Each line feeds one winding directly, which explains the current equality. The line voltage is the difference of phase voltages 120° apart:

VL=2Vphcos⁡30∘=3Vph

It is not twice phase voltage. A 230/400 V star supply has about 230 V line to neutral and 400 V line to line. Other nominal pairs include 120/208 V, 277/480 V and 115/200 V.

In delta, the windings form a closed loop, each directly between two lines. Each winding therefore receives line voltage. A line conductor joins two winding branches, and its current is their phasor difference. A delta has no star point and no neutral.

Compare the same heating elements

Connect three equal 46 Ω elements to a 400 V line supply. In delta each receives 400 V:

Iph=400/46≈8.70 A IL=3(400/46)≈15.1 A

Total power is 3(4002/46)≈10.4 kW.

In star each receives 400/3≈231 V. Phase and line current are both about 5.02 A, and total power is about 3.48 kW. With the same elements and line voltage, delta gives three times the star power and three times the line current. The change comes from the voltage across each resistance.

Interpret supply readings

On a healthy 230/400 V supply, any line-to-line pair reads about 400 V and each line-to-neutral pair about 230 V. Neutral to earth is normally close to zero. One 230 V measurement between unidentified conductors cannot identify them: line to neutral, line to protective earth, and line to line on a 230 V network can produce that reading.

Parts of Belgium also have 3 × 230 V networks with three lines and no distributed neutral. Single-phase loads then connect between two lines. A motor labeled 230/400 V Δ/Y uses delta on that 230 V line supply and star on a 400 V line supply. Always attach the supply voltage to a conductor pair before attaching it to a winding.

Key Takeaways

  • Three-phase voltages are separated by 120 electrical degrees.
  • Phase values belong to one winding or element; line values belong to supply conductors.
  • Balanced star voltage uses VL=3Vph, while star currents are equal.
  • Delta voltages are equal; balanced delta current uses IL=3Iph.
  • The same resistive elements take three times the power in delta as in star at the same line voltage.
  • One voltage measurement cannot establish unidentified conductors’ functions.

5.3 Three-phase power and load balance

A balanced load has equal phase impedances. On a balanced source its currents have equal magnitudes and remain 120° apart. You can calculate total power from one phase and multiply by three, or use line quantities directly.

Use the right voltage and current pair

For balanced sinusoidal three-phase loads in star or delta:

S=3VLIL P=3VLILcos⁡φ,Q=3VLILsin⁡φ

The phase form of active power is P=3VphIphcos⁡φ. Use line voltage with line current in the first formula, or phase voltage with phase current in the second. Mixing them adds or removes a factor of 3.

A motor on 400 V takes 10 A per line at power factor 0.85. Apparent power is 3×400×10≈6.93 kVA. Active input is about 5.89 kW; reactive power is about 3.65 kvar.

To find line current from active input:

IL=P3VLcos⁡φ

An 11 kW electrical load on 400 V at 0.86 power factor takes about 18.5 A per line. An 11 kW shaft-output label would need an efficiency conversion before this calculation.

Explain the neutral current

Three equal sinusoidal currents 120° apart add to zero at the neutral. With unequal currents, cancellation is incomplete. For three loads having the same power-factor angle:

IN=I12+I22+I32−I1I2−I2I3−I3I1

With 10 A, 8 A and 6 A resistive loads, the quantity inside the square root is:

100+64+36−80−48−60=12

Neutral current is therefore 12≈3.46 A. It is not the 4 A difference between largest and smallest current. For 10 A, 10 A and 4 A it is 6 A; for 16 A, 16 A and zero it is 16 A. The relative directions are part of the sum.

The formula's equal-power-factor-angle condition matters. If branch currents have different phase shifts, their directions need separate treatment. Likewise, the balanced three-phase power formula is not a shortcut for an arbitrary unbalanced load; use the actual phase powers.

Share the load across phases

Distribute single-phase loads across L1, L2 and L3. Better balance reduces the largest line current and usually lowers neutral current and losses. It also helps keep phase voltages even. Unequal phase voltages can make a three-phase motor run hotter. Balanced sinusoidal three-phase power is constant in time, giving smoother motor torque than single-phase power.

An open neutral in an unbalanced star system lets the load star point move. Some loads can then receive voltages approaching line voltage instead of their intended line-to-neutral voltage, damaging equipment.

Electronic loads add a second issue: their third-harmonic currents can reinforce in the neutral. Equal rms currents on all three lines therefore do not guarantee zero neutral current when the waveforms are distorted.

Key Takeaways

  • Balanced three-phase power uses line voltage and line current with 3.
  • Shaft output requires efficiency to obtain electrical input power.
  • Equal sinusoidal currents 120° apart cancel in the neutral.
  • Unbalanced neutral current is a directional sum, not a simple difference.
  • The stated neutral formula requires equal power-factor angles.
  • A broken neutral can expose loads to excessive voltage.
  • Third-harmonic currents can add in the neutral despite equal line rms currents.

5.4 Motors, chargers and aircraft equipment

Three-phase currents in stator windings create a rotating magnetic field. This connects supply frequency with motor speed, while the winding voltage determines the correct star or delta connection. The same three-phase ideas also appear inside vehicle drives and aircraft electrical systems.

Relate frequency to speed

The rotating field's synchronous speed is:

ns=60fp

Here p is the number of pole pairs. With two pairs, synchronous speed is 1500 rpm at 50 Hz and 1800 rpm at 60 Hz. An induction motor rotor turns slightly slower under normal motoring conditions. At 1450 rpm against a 1500 rpm field, slip is (1500−1450)/1500≈0.0333, or about 3.3%.

Phase sequence sets field direction. Interchanging any two lines reverses it. Direction is checked before a pump, fan or compressor enters service because some equipment can be damaged by reverse rotation. Losing one line is different: a running motor may continue with excessive current and heating, while a stopped motor may only hum. Overload and phase-failure protection address that condition.

Read the winding rating

A nameplate reading 230/400 V Δ/Y means each winding is rated 230 V. On a 400 V line supply, use star:

Vph=400/3≈231 V

On a 230 V line supply, use delta and each winding receives 230 V. Delta on 400 V would place 400 V across a 230 V winding and cause severe overheating. Terminal links establish the connection; the two nameplate numbers belong to their stated connection symbols.

Star-delta starting applies to a motor intended to run in delta at the available line voltage. Starting in star reduces winding voltage to 1/3 of direct-delta voltage. Starting line current and starting torque are each about one third of direct-delta values. On a 400 V supply, a 400/690 V Δ/Y motor can run in delta; a 230/400 V Δ/Y motor must run in star and is not suitable for that star-delta changeover.

Follow energy through an electric vehicle

A vehicle battery stores DC. During AC charging, the on-board charger rectifies supply AC to charge the battery. A 230 V, 32 A single-phase connection offers about 7.4 kW at unity power factor. A compatible charger on 400 V three-phase at 16 A per line can take about 3×400×16=11.1 kW.

For propulsion, an inverter converts battery DC into three-phase AC with controlled frequency and voltage. Frequency controls the motor field speed. During regenerative braking, the motor generates and the inverter returns energy to the battery. A building variable-speed drive similarly rectifies incoming AC and creates an adjustable-frequency three-phase output for a pump or compressor.

Recognize aircraft supplies

A common aircraft supply is 115/200 V, three-phase, 400 Hz: about 115 V phase to neutral and 200 V line to line. The higher frequency permits smaller transformers and motors. Pumps and galley ovens can use the AC supply; transformer-rectifier units provide 28 V DC equipment power. Some newer aircraft use variable-frequency generation, roughly 360–800 Hz, following engine speed. Supply frequency and connection are therefore both part of the equipment match.

Key Takeaways

  • Synchronous speed depends on frequency and pole pairs.
  • An induction rotor normally runs below synchronous speed.
  • A Δ/Y nameplate states the line voltages for each connection.
  • Star-delta starting requires a motor rated to run in delta on that supply.
  • EV chargers convert AC to DC; traction inverters create controlled three-phase AC.
  • Aircraft commonly use 115/200 V at 400 Hz, with other generation arrangements also in service.

Alternating Current examples

5 Walkthroughs

1

Read a trace and find its rated values

12 steps
Read a full cycle, calculate frequency and instantaneous voltage, then convert a trace into peak and rms values.
  1. 1
    IntroductionTwo scales, two questions

    A waveform has a time scale and a voltage scale. The time scale tells you how often its pattern repeats; the voltage scale tells you how far it moves above and below zero.

    You will read a 50 Hz sine wave, then turn its peak measurement into an rms value. Keep the two jobs separate: a faster waveform need not be taller.

  2. 2
    ExplanationMark one complete cycle

    Start at an upward zero crossing. Follow the trace to its positive peak, down through zero, to its negative peak, then back to the next upward crossing. That is one complete cycle, or 360°.

    The first peak is at 90°, the next zero crossing at 180° and the negative peak at 270°. Two adjacent zero crossings are only half a cycle apart, so their spacing cannot be used directly as the full period.

  3. 3
    ExampleTurn divisions into a period

    The trace takes four horizontal divisions for one full cycle. The time setting is 5 ms per division, so multiply the span by the scale:

    T=4×5=20 ms

    Convert this to 0.020 s before calculating frequency. Measuring between two positive peaks would give the same full-cycle time.

  4. 4
    ExampleTake the reciprocal

    Continue with the 0.020 s period. Frequency counts how many of those cycles fit into a second:

    f=10.020=50 Hz

    A 60 Hz wave would take about 16.7 ms per cycle; a 400 Hz wave would take only 2.5 ms. The smaller time per cycle means more cycles each second. Entering 20 instead of 0.020 would turn a millisecond reading into an incorrect frequency.

  5. 5
    ExampleFind a point inside the cycle

    The same wave has a peak of 325 V. At 2.5 ms after its upward zero crossing, its angle is:

    θ=360∘×50×0.0025=45∘

    Use degree mode, then calculate:

    v=325sin⁡45∘≈230 V

    This is an instantaneous value at one time. At the 90° peak the same waveform reaches 325 V.

  6. 6
    ChallengeRead a new time scale

    A reduced-voltage waveform takes five divisions per cycle at 0.5 ms/div. What frequency does it have?

    ---reveal---

    The period is 5×0.5=2.5 ms=0.0025 s. Therefore f=1/0.0025=400 Hz.

  7. 7
    ExampleRead the vertical span

    The 50 Hz trace spans 6.5 vertical divisions from negative peak to positive peak at 100 V/div:

    Vpp=6.5×100=650 V

    Because it is symmetrical about zero, the peak is half the full span, or 325 V. This reading covers both sides of zero. Using all 650 V as the peak would double every later peak-based calculation.

  8. 8
    ExplanationConvert peak into rms

    The rms value describes the DC-equivalent heating effect in a resistor. For this sine wave:

    Vrms=3252≈230 V

    Both halves of the cycle heat a resistor because current reverses with voltage. The signed average voltage is zero, but its heating value is not. An average-responding meter scales its rectified average to show rms only when the waveform is sinusoidal.

  9. 9
    ChallengeCheck a low-voltage sine wave

    A sine wave is symmetrical about zero and measures 72 V peak to peak. What rms voltage should a suitable AC meter show?

    ---reveal---

    Peak voltage is 72/2=36 V. Its rms value is 36/2≈25.5 V.

    A reading calculated as 72/2 would use the full peak-to-peak span as the peak.

  10. 10
    TipChoose a meter for the waveform

    A drive can draw current in pulses even when its supply voltage looks sinusoidal. An average-responding meter's fixed scaling does not correctly describe every pulse shape.

    Use a true-rms meter suited to the waveform's frequency content and measurement ratings. The sine-wave relationship between peak and rms also depends on shape: a symmetrical square wave has rms equal to its peak magnitude.

  11. 11
    ChallengeCombine both scale readings

    A zero-centered sine wave spans six vertical divisions at 4 V/div. One cycle takes eight horizontal divisions at 0.25 ms/div. Find its frequency and rms voltage.

    ---reveal---

    The period is 2 ms, or 0.002 s, giving 500 Hz. Peak-to-peak voltage is 24 V, so peak is 12 V and rms is 12/2≈8.49 V.

  12. 12
    RecapLabel the value before using it

    Before using a waveform reading in an equipment calculation, attach its meaning: full-cycle time, frequency, instantaneous value, peak, peak to peak or rms.

    A heater calculation needs rms voltage. A waveform peak matters to insulation stress. A generator-frequency check needs both pole pairs and rpm.

2

Predict current timing and reactance

14 steps
Use phase relationships to distinguish a resistor, coil and capacitor, then predict current changes as frequency changes.

Save this lesson to follow every Walkthrough step by step.

  1. 1
    IntroductionWhat sets current timing?
  2. 2
    ExplanationRead lead and lag
  3. 3
    ExampleStart with a resistor
  4. 4
    ChallengeInterpret a time delay
  5. 5
    ExplanationA coil opposes current change
  6. 6
    ExampleConvert reactance into current
  7. 7
    ChallengeChange frequency without changing the coil
  8. 8
    Key InsightUse measurements for a real coil
  9. 9
    ExplanationA capacitor responds to voltage change
  10. 10
    ExampleCalculate capacitor opposition
  11. 11
    ChallengeTest the capacitor’s response
  12. 12
    ConnectionConnect the rule to a filter
  13. 13
    ChallengeCompare two ideal branches
  14. 14
    RecapMake a physical prediction first
3

Solve series and parallel mixed circuits

17 steps
Work through impedance and current triangles, resonance, and the combination of real parallel loads.

Save this lesson to follow every Walkthrough step by step.

  1. 1
    IntroductionChoose the shared quantity
  2. 2
    ExplanationDraw the series triangle
  3. 3
    ExampleFind the common current
  4. 4
    ExampleRecover the component voltages
  5. 5
    ExampleFind the phase angle
  6. 6
    ChallengeSolve a new RC circuit
  7. 7
    ExampleAdd the opposing reactive parts
  8. 8
    Key InsightCheck the larger internal voltages
  9. 9
    ExplanationLocate series resonance
  10. 10
    ChallengePredict a resonance change
  11. 11
    ExplanationSwitch from voltages to currents
  12. 12
    ExampleWork a parallel current triangle
  13. 13
    ChallengeApply cancellation in a new case
  14. 14
    ExampleSplit a real motor’s current
  15. 15
    ConnectionDistinguish the two resonances
  16. 16
    ChallengeCombine a motor, heater and capacitor
  17. 17
    RecapCheck the circuit arrangement
4

Size a capacitor correction

15 steps
Calculate active, reactive and apparent power, then reduce a lagging supply demand without changing the motor’s active input.

Save this lesson to follow every Walkthrough step by step.

  1. 1
    IntroductionSeparate energy conversion from demand
  2. 2
    ExampleCalculate apparent and active power
  3. 3
    ExampleComplete the power triangle
  4. 4
    ChallengeUse a new power triangle
  5. 5
    ExplanationFind the current penalty
  6. 6
    ChallengeInterpret measured power
  7. 7
    TipCheck what the meter’s angle means
  8. 8
    ExplanationSet a correction target
  9. 9
    ExampleFind the reactive reduction
  10. 10
    ExampleTurn reactive power into capacitance
  11. 11
    Key InsightIdentify what changes
  12. 12
    ChallengeCalculate another correction
  13. 13
    ConnectionLet the correction follow the load
  14. 14
    ChallengeCombine the power and current checks
  15. 15
    RecapCheck power before judging savings
5

Match supply values to real equipment

20 steps
Read split-phase, star and delta supplies, calculate balanced power and neutral current, and choose a motor connection from its winding rating.

Save this lesson to follow every Walkthrough step by step.

  1. 1
    IntroductionRead the conductor pair first
  2. 2
    ExplanationFollow the normal current path
  3. 3
    ExplanationRecognize a center-tapped source
  4. 4
    ChallengeCalculate a single-phase input
  5. 5
    ExplanationSeparate line from winding
  6. 6
    ExplanationUse star relationships
  7. 7
    ExplanationUse delta relationships
  8. 8
    ExampleCompare the same heating elements
  9. 9
    ChallengeConvert a new connection
  10. 10
    ExplanationCalculate balanced three-phase power
  11. 11
    ExampleRead the neutral’s cancellation
  12. 12
    ChallengeRemove one phase load
  13. 13
    Key InsightKnow where cancellation fails
  14. 14
    ExplanationConnect frequency with motor speed
  15. 15
    ExplanationRead a Δ/Y nameplate
  16. 16
    ChallengeCheck a proposed starter
  17. 17
    ConnectionFollow power through a vehicle
  18. 18
    ConnectionRecognize an aircraft system
  19. 19
    ChallengeCombine charging current and neutral balance
  20. 20
    RecapMatch values to the equipment

Alternating Current practice questions

60 Practice Questions in 6 sets

Set 1: Read waveforms and component timing10 Practice Questions

Question 1 of 10

A sine wave repeats every 0.0125 s. What is its frequency?
  1. 0.0125 Hz
  2. 12.5 Hz
  3. 80 Hz
  4. 800 Hz
Show answerHide answer
Answer: C
Frequency is the reciprocal of period, so 1/0.0125=80 Hz. A period of 12.5 ms is not a frequency of 12.5 Hz; it is a time measurement that must first be expressed in seconds. A larger frequency would require a correspondingly shorter cycle.

Question 2 of 10

Two upward zero crossings are 6 divisions apart on a 2 ms/div oscilloscope scale. What frequency does the trace represent?
  1. About 41.7 Hz
  2. About 83.3 Hz
  3. About 166.7 Hz
  4. About 0.0833 Hz
Show answerHide answer
Answer: B
The matching upward crossings enclose one full cycle: 6×2=12 ms=0.012 s. Its reciprocal is about 83.3 Hz. Treating the span as half a cycle would give 41.7 Hz after doubling the period, but the crossings already have the same direction.

Question 3 of 10

A six-pole generator must supply 60 Hz. At what speed must it turn?
  1. 1200 rpm
  2. 600 rpm
  3. 1800 rpm
  4. 3600 rpm
Show answerHide answer
Answer: A
Six poles form three pole pairs, so n=60f/p=60×60/3=1200 rpm. Using six as the pole-pair count would give 600 rpm. The pair count, not the number of individual north and south poles, determines the cycles per revolution.

Question 4 of 10

A sinusoidal current has a peak of 12 A. What is its rms value?
  1. About 16.97 A
  2. About 6.00 A
  3. About 7.64 A
  4. About 8.49 A
Show answerHide answer
Answer: D
For a sine wave, divide peak current by the square root of two: 12/2≈8.49 A. Multiplying would give 16.97 A and would make rms larger than peak. The factor 0.637 instead gives a half-cycle average, which measures a different feature.

Question 5 of 10

A zero-centered sine-wave trace spans 8 divisions peak to peak at 5 V/div. What rms voltage does it represent?
  1. About 28.3 V
  2. About 14.1 V
  3. About 20.0 V
  4. About 56.6 V
Show answerHide answer
Answer: B
The full vertical span is 40 V peak to peak, so the peak is 20 V and rms is 20/2≈14.1 V. Dividing 40 V directly by the square root of two would give 28.3 V. That misses the conversion from peak to peak into peak.

Question 6 of 10

Why can a resistor warm up on a sine-wave supply whose signed average voltage is zero?
  1. Voltage keeps one polarity while current reverses, storing heat between peaks.
  2. Current stays positive while voltage reverses, canceling only its negative power.
  3. Voltage and current reverse together, keeping their product nonnegative.
  4. Only the positive voltage half heats the resistor, balancing the negative voltage.
Show answerHide answer
Answer: C
A resistor’s voltage and current are in phase, so both are negative during the negative half cycle. Their product is positive there, just as it is in the positive half cycle. Heating therefore occurs in both halves; a zero signed voltage average does not make the average of voltage times current zero.

Question 7 of 10

Voltage reaches a positive peak 0.5 ms before current on two same-frequency traces. How is the timing described?
  1. Current lags voltage.
  2. Current leads voltage.
  3. Current is in phase.
  4. Current is in antiphase.
Show answerHide answer
Answer: A
Voltage reaches the matching peak first, so it leads and current lags. Calling current leading would reverse the observed order. The delay alone establishes the direction, but a numerical angle would also require the cycle period; the 0.5 ms delay does not by itself mean a half-cycle shift.

Question 8 of 10

At 80 Hz, a current peak occurs 1.5625 ms after the voltage peak. What is its phase relationship?
  1. 45° leading
  2. 90° lagging
  3. 90° leading
  4. 45° lagging
Show answerHide answer
Answer: D
The period is 1/80=12.5 ms, so the delay is one eighth of a cycle, or 45°. Current arrives later, making the relationship lagging. A 90° delay would be a quarter cycle, or 3.125 ms here, not the stated 1.5625 ms.

Question 9 of 10

An ideal 80 mH inductor is supplied at 75 Hz. What is its reactance?
  1. About 3.77 Ω
  2. About 37.7 Ω
  3. About 59.7 Ω
  4. About 37700 Ω
Show answerHide answer
Answer: B
Convert 80 mH to 0.080 H, then calculate 2π×75×0.080≈37.7 Ω. Entering 80 as henries would give about 37700 Ω. The milli prefix changes the input by a thousand and must be handled before applying the reactance formula.

Question 10 of 10

An ideal capacitor carries 0.60 A at 100 Hz on 24 V. It is replaced by a capacitor with twice the capacitance, and frequency is reduced to 25 Hz at the same voltage. What current results?
  1. 0.15 A
  2. 0.60 A
  3. 1.20 A
  4. 0.30 A
Show answerHide answer
Answer: D
Capacitive current at fixed voltage is proportional to frequency times capacitance. Frequency becomes one quarter and capacitance doubles, so current becomes one half: 0.30 A. Doubling current to 1.20 A accounts for the new capacitor but misses the opposing effect of the lower frequency.
Set 2: Choose the right circuit calculation10 Practice Questions

Save this lesson to see every answer and practice every set.

Question 1 of 10

A series RL load takes 3 A from 150 V and dissipates 270 W. What are its resistance and inductive reactance?
  1. 40 Ω resistance; 30 Ω reactance
  2. 30 Ω resistance; 40 Ω reactance
  3. 30 Ω resistance; 20 Ω reactance
  4. 50 Ω resistance; 40 Ω reactance
Show answerHide answer

Save this lesson to see this answer.

Question 2 of 10

A series RLC circuit has R = 15 Ω, X_L = 44 Ω and X_C = 36 Ω on 85 V. What are supply current and phase relationship?
  1. 5 A, leading
  2. 1.04 A, lagging
  3. 5 A, lagging
  4. 3.70 A, lagging
Show answerHide answer

Save this lesson to see this answer.

Question 3 of 10

Parallel ideal resistor and inductor branches draw 15 A and 8 A from one supply. What current does the supply carry?
  1. 17 A
  2. 23 A
  3. 7 A
  4. 13 A
Show answerHide answer

Save this lesson to see this answer.

Question 4 of 10

A 48 Ω pure resistor is connected to 96 V rms AC. What rms current flows?
  1. 2 A
  2. 0.5 A
  3. 1.41 A
  4. 2.83 A
Show answerHide answer

Save this lesson to see this answer.

Question 5 of 10

An ideal inductor has 25 Ω reactance at 40 Hz. What is its reactance at 120 Hz?
  1. 8.33 Ω
  2. 25 Ω
  3. 225 Ω
  4. 75 Ω
Show answerHide answer

Save this lesson to see this answer.

Question 6 of 10

A coil has 9 Ω winding resistance and draws 4 A at 60 V rms. What inductive reactance does its series RL model have?
  1. 6 Ω
  2. 12 Ω
  3. 15 Ω
  4. 24 Ω
Show answerHide answer

Save this lesson to see this answer.

Question 7 of 10

What is the reactance of a 25 µF ideal capacitor at 200 Hz?
  1. About 318 Ω
  2. About 0.0318 Ω
  3. About 31.8 Ω
  4. About 78.5 Ω
Show answerHide answer

Save this lesson to see this answer.

Question 8 of 10

An ideal capacitor’s capacitance is halved while supply frequency stays fixed. How does its reactance change?
  1. It halves.
  2. It stays unchanged.
  3. It becomes four times larger.
  4. It doubles.
Show answerHide answer

Save this lesson to see this answer.

Question 9 of 10

A series circuit has 20 Ω resistance and 21 Ω inductive reactance on 116 V. What rms current does it draw?
  1. 4 A
  2. 2.83 A
  3. 5.52 A
  4. 5.80 A
Show answerHide answer

Save this lesson to see this answer.

Question 10 of 10

An RC series circuit has 40 Ω resistance and 30 Ω capacitive reactance. What is the current’s phase angle relative to the supply?
  1. About 36.9° lagging
  2. About 53.1° leading
  3. About 36.9° leading
  4. About 53.1° lagging
Show answerHide answer

Save this lesson to see this answer.

Set 3: Diagnose mixed circuits and resonance10 Practice Questions

Save this lesson to see every answer and practice every set.

Question 1 of 10

A series RLC circuit is at resonance. What is its supply power factor?
  1. 0
  2. 0.5
  3. 0.707
  4. 1
Show answerHide answer

Save this lesson to see this answer.

Question 2 of 10

A series RC circuit takes 2 A. Its resistance is 18 Ω and capacitive reactance is 24 Ω. What supply voltage is required?
  1. 84 V
  2. 36 V
  3. 60 V
  4. 48 V
Show answerHide answer

Save this lesson to see this answer.

Question 3 of 10

A series RL circuit takes 2.4 A from 120 V. The resistor voltage is 72 V. What inductance does its ideal-inductor model require at 50 Hz?
  1. About 127 mH
  2. About 95.5 mH
  3. About 159 mH
  4. About 76.4 mH
Show answerHide answer

Save this lesson to see this answer.

Question 4 of 10

A series RLC circuit has 32 Ω inductive reactance and 50 Ω capacitive reactance at 100 Hz. Its resistance is 24 Ω. At 200 Hz, what is its impedance magnitude?
  1. About 30.0 Ω
  2. About 45.8 Ω
  3. About 92.2 Ω
  4. About 63.2 Ω
Show answerHide answer

Save this lesson to see this answer.

Question 5 of 10

A series circuit has R = 10 Ω and L = 40 mH on a fixed 80 V rms supply. A capacitor is chosen to make it resonant at 250 Hz. About what rms voltage appears across that capacitor?
  1. 503 V
  2. 80 V
  3. 251 V
  4. 63 V
Show answerHide answer

Save this lesson to see this answer.

Question 6 of 10

Why is voltage the natural reference quantity for a parallel AC circuit?
  1. Every branch carries the same current.
  2. All branch currents are in phase.
  3. Every branch has the same voltage.
  4. All branch impedances are equal.
Show answerHide answer

Save this lesson to see this answer.

Question 7 of 10

Parallel ideal branches take 16 A resistive, 18 A inductive and 6 A capacitive current. What is the total current?
  1. 40 A
  2. 20 A
  3. 28 A
  4. 8 A
Show answerHide answer

Save this lesson to see this answer.

Question 8 of 10

A motor draws 13 A at power factor 12/13 lagging. A parallel heater takes 3 A and an ideal parallel capacitor takes 5 A at the same voltage. What supply current results?
  1. 21 A
  2. 16.6 A
  3. 10 A
  4. 15 A
Show answerHide answer

Save this lesson to see this answer.

Question 9 of 10

An RC series circuit takes 1 A from 65 V at 50 Hz and dissipates 33 W. What is its current at 100 Hz, with the same resistor, capacitor and voltage?
  1. About 2.00 A
  2. About 0.50 A
  3. About 1.50 A
  4. About 1.97 A
Show answerHide answer

Save this lesson to see this answer.

Question 10 of 10

At 100 Hz, parallel ideal branches draw 6 A resistive, 10 A inductive and 4 A capacitive current. Frequency doubles at fixed voltage and fixed component values. What is the new supply current?
  1. About 6.71 A, lagging
  2. About 6.71 A, leading
  3. About 8.49 A, leading
  4. About 13.0 A, leading
Show answerHide answer

Save this lesson to see this answer.

Set 4: Calculate demand and capacitor correction10 Practice Questions

Save this lesson to see every answer and practice every set.

Question 1 of 10

Three parallel sinusoidal loads take 1.2 kW and 1.6 kvar inductive, 0.8 kW at unity power factor, and 1.6 kvar capacitive. What is their combined apparent demand?
  1. 3.2 kVA
  2. 3.6 kVA
  3. 4.8 kVA
  4. 2.0 kVA
Show answerHide answer

Save this lesson to see this answer.

Question 2 of 10

A 6 kW load at power factor 0.8 lagging is corrected to unity. How much capacitive reactive power is required?
  1. 1.5 kvar
  2. 4.5 kvar
  3. 3.6 kvar
  4. 7.5 kvar
Show answerHide answer

Save this lesson to see this answer.

Question 3 of 10

A 4 kW sinusoidal load on 200 V, 50 Hz is corrected from 0.8 lagging to 0.96 lagging. What single-phase capacitance is needed?
  1. About 146 µF
  2. About 239 µF
  3. About 73 µF
  4. About 93 µF
Show answerHide answer

Save this lesson to see this answer.

Question 4 of 10

A single-phase load takes 6 A rms at 240 V rms. What is its apparent power?
  1. 1.44 kW
  2. 1.44 kVA
  3. 0.694 kVA
  4. 0.144 kVA
Show answerHide answer

Save this lesson to see this answer.

Question 5 of 10

A sinusoidal single-phase load has 2.4 kW active power and 1.8 kvar inductive reactive power. What is its apparent power?
  1. 3.0 kVA
  2. 4.2 kVA
  3. 0.6 kVA
  4. 2.1 kVA
Show answerHide answer

Save this lesson to see this answer.

Question 6 of 10

A sinusoidal load uses 1260 W while taking 7 A from 225 V. What is its power factor?
  1. 0.64
  2. 0.90
  3. 1.25
  4. 0.80
Show answerHide answer

Save this lesson to see this answer.

Question 7 of 10

Two single-phase sinusoidal loads each take 4 kW from 200 V. One has power factor 0.6 and the other 0.9. With equal cable resistances, how do their cable losses compare?
  1. The 0.6 load causes 1.50 times the loss.
  2. The 0.6 load causes 0.44 times the loss.
  3. The 0.6 load causes 2.25 times the loss.
  4. The 0.6 load causes 3.38 times the loss.
Show answerHide answer

Save this lesson to see this answer.

Question 8 of 10

A single-phase sinusoidal motor takes 5 kW and 3.75 kvar inductive from 250 V. An ideal parallel capacitor supplies 2.25 kvar. What is the corrected supply current?
  1. About 25.0 A
  2. About 16.0 A
  3. About 20.9 A
  4. About 29.2 A
Show answerHide answer

Save this lesson to see this answer.

Question 9 of 10

A power analyzer reports a distorted load current, true power factor 0.72 and displacement power factor 0.99. What explains these readings?
  1. Distortion adds rms current beyond the near-in-phase fundamental contribution.
  2. The fundamental current must lag by the angle whose cosine is 0.72.
  3. The load converts only 72% of its active input into useful output.
  4. The watt reading must exceed the rms voltage-current product by 27%.
Show answerHide answer

Save this lesson to see this answer.

Question 10 of 10

At full load, a fixed ideal capacitor exactly cancels a motor’s 6 kvar inductive demand. At lighter load the motor takes 2 kW and 2 kvar inductive on the same 200 V supply. What supply current and power-factor direction result?
  1. About 14.1 A, lagging
  2. About 22.4 A, lagging
  3. About 10.0 A, unity
  4. About 22.4 A, leading
Show answerHide answer

Save this lesson to see this answer.

Set 5: Read supply labels and winding connections10 Practice Questions

Save this lesson to see every answer and practice every set.

Question 1 of 10

What voltage is available between the two hot ends of a nominal 110/220 V center-tapped single-phase winding?
  1. 110 V
  2. 190.5 V
  3. 220 V
  4. 0 V
Show answerHide answer

Save this lesson to see this answer.

Question 2 of 10

In a delta-connected load, where is each winding connected?
  1. Between two line conductors.
  2. Between one line and neutral.
  3. Between neutral and protective earth.
  4. Between two common star points.
Show answerHide answer

Save this lesson to see this answer.

Question 3 of 10

A sinusoidal single-phase compressor takes 2.16 kW electrical input at power factor 0.75 on 240 V. What rms current does it draw?
  1. 9 A
  2. 6.75 A
  3. 16 A
  4. 12 A
Show answerHide answer

Save this lesson to see this answer.

Question 4 of 10

A balanced star load receives 480 V line to line. What voltage appears across each winding?
  1. 480 V
  2. About 277 V
  3. 240 V
  4. About 831 V
Show answerHide answer

Save this lesson to see this answer.

Question 5 of 10

A balanced delta load has 9 A through each winding. What current flows in each supply line?
  1. About 15.6 A
  2. 9 A
  3. About 5.20 A
  4. 27 A
Show answerHide answer

Save this lesson to see this answer.

Question 6 of 10

An earth-referenced supply has unidentified conductors and no known network arrangement. A rated meter reads 230 V between two of them. What conductor identification is justified by that reading alone?
  1. They must be line and neutral; the neutral is the lower-potential one.
  2. They must be two lines; line-to-neutral voltage would be lower.
  3. Their voltage difference is known; their functions remain unconfirmed.
  4. They must be line and earth; earth reference excludes a neutral.
Show answerHide answer

Save this lesson to see this answer.

Question 7 of 10

Three equal 80 Ω resistors are connected in star to a 400 V line supply. They are then reconnected in delta on that same supply. How does line current change?
  1. From about 2.89 A to 5.00 A.
  2. From about 5.00 A to 8.66 A.
  3. From about 5.00 A to 15.0 A.
  4. From about 2.89 A to 8.66 A.
Show answerHide answer

Save this lesson to see this answer.

Question 8 of 10

Three sinusoidal loads, all at power factor 0.8 lagging, take 14 A, 10 A and 6 A from the phases of a balanced star supply with neutral. What is the neutral-current magnitude?
  1. 8.00 A
  2. About 6.93 A
  3. About 17.9 A
  4. 4.00 A
Show answerHide answer

Save this lesson to see this answer.

Question 9 of 10

A balanced sinusoidal three-phase heater draws 12 A per line from a 415 V line supply. What active power does it take?
  1. About 8.63 kW
  2. About 4.98 kW
  3. About 14.9 kW
  4. About 6.10 kW
Show answerHide answer

Save this lesson to see this answer.

Question 10 of 10

A 400 V line supply feeds a motor rated 400/690 V Δ/Y. It will use star-delta starting. What winding voltage applies in its starting and running connections?
  1. 400 V starting; about 231 V running.
  2. About 231 V starting; 690 V running.
  3. About 231 V starting; 400 V running.
  4. 400 V starting; 690 V running.
Show answerHide answer

Save this lesson to see this answer.

Set 6: Solve equipment and supply problems10 Practice Questions

Save this lesson to see every answer and practice every set.

Question 1 of 10

What does an EV on-board charger do during AC charging?
  1. It converts battery DC into AC for the motor.
  2. It converts supply AC into DC for the battery.
  3. It reverses motor phase sequence to charge.
  4. It stores three-phase AC directly in the cells.
Show answerHide answer

Save this lesson to see this answer.

Question 2 of 10

An aircraft has a balanced 115 V phase-to-neutral AC supply. What is its approximate line-to-line voltage?
  1. 115 V
  2. 230 V
  3. 66.4 V
  4. 199 V
Show answerHide answer

Save this lesson to see this answer.

Question 3 of 10

A balanced three-phase load takes 14.4 kW electrical input from 480 V at power factor 0.8. What are its line current and apparent power?
  1. About 37.5 A; 18.0 kVA
  2. About 21.7 A; 11.52 kVA
  3. About 21.7 A; 18.0 kVA
  4. About 17.3 A; 14.4 kVA
Show answerHide answer

Save this lesson to see this answer.

Question 4 of 10

A six-pole induction motor runs at 1164 rpm on 60 Hz. What is its slip as a percentage of synchronous speed?
  1. 3.0%
  2. 2.0%
  3. 35.3%
  4. 51.5%
Show answerHide answer

Save this lesson to see this answer.

Question 5 of 10

Three equal sinusoidal line-to-neutral resistive loads on a 240 V phase supply each draw 9 A. One load opens while the neutral remains intact. What are the total active power and neutral current now?
  1. 4.32 kW; 0 A
  2. 6.48 kW; 9 A
  3. 4.32 kW; 9 A
  4. 4.32 kW; 18 A
Show answerHide answer

Save this lesson to see this answer.

Question 6 of 10

A 230/400 V Δ/Y motor is available for a 400 V line supply. A proposed starter begins in star and then changes to delta. What must change in this plan?
  1. Keep this motor in delta; star would exceed its winding rating.
  2. Keep this motor in star; it cannot run in delta on 400 V.
  3. Use the changeover as planned; both ratings apply to each winding.
  4. Reverse two lines at changeover; this reduces delta winding voltage.
Show answerHide answer

Save this lesson to see this answer.

Question 7 of 10

A sinusoidal motor has power factor 0.8 and efficiency 0.9. Which ratio does the 0.9 describe?
  1. Useful shaft output divided by active electrical input.
  2. Active electrical input divided by apparent electrical input.
  3. Reactive electrical input divided by active electrical input.
  4. Useful shaft output divided by apparent electrical input.
Show answerHide answer

Save this lesson to see this answer.

Question 8 of 10

A balanced 400 V three-phase motor takes 8 kW electrical input at power factor 0.8 lagging. A heater adds 6 kW equally across the phases. What is the combined line current?
  1. About 23.1 A
  2. About 20.2 A
  3. About 25.3 A
  4. About 22.0 A
Show answerHide answer

Save this lesson to see this answer.

Question 9 of 10

An aircraft winding rated 100 V at 400 Hz is modeled as 10 Ω resistance in series with 30 mH inductance. What current would this model draw at the same voltage but 50 Hz?
  1. About 1.31 A
  2. About 10.0 A
  3. About 0.168 A
  4. About 7.28 A
Show answerHide answer

Save this lesson to see this answer.

Question 10 of 10

Three electronic loads draw equal rms currents from the three phases, but the neutral carries a large current. Their voltage supply is balanced. What explains this without contradicting the readings?
  1. Equal fundamental currents become 180° apart when a neutral is fitted.
  2. Third-harmonic current contributions can reinforce in the neutral.
  3. The neutral current must equal the arithmetic sum of all fundamental currents.
  4. Each load must be drawing its return current through protective earth.
Show answerHide answer

Save this lesson to see this answer.

Stuck on your own question? Homework Help

Key Terms

76 Key Terms, each with its definition

A

Active power
Active power is the average rate of electrical energy conversion into heat, light or work, measured in watts.
A motor taking 2300 VA at power factor 0.8 has 1840 W active electrical input before output losses are considered.
Alternating current
Alternating current is electric current that regularly reverses direction, commonly following a repeating sinusoidal waveform.
A generator or inverter can supply AC to a motor, while a vehicle battery stores energy as a DC source.
Apparent power
Apparent power is the product of rms voltage and rms current, measured in volt-amperes and indicating the supply's current burden.
A 230 V load drawing 10 A demands 2300 VA whether its power factor is 1 or a lower value.
Average-responding meter
An average-responding AC meter measures rectified average and scales it to display rms correctly for a sinusoidal input waveform.
Its sine-wave calibration can give an inaccurate rms reading when an LED driver draws current in narrow pulses.

B

Balanced load
A balanced three-phase load has equal phase impedances and takes equal currents 120° apart when connected to a balanced sinusoidal supply.
Three equal resistive phase loads cancel their fundamental currents at the neutral and share the source evenly.
Branch current
A branch current is the current flowing in one path of a parallel circuit, with its own magnitude and phase relative to the shared voltage.
A parallel resistor, inductor and capacitor can each carry more current than their net contribution to the supply suggests.

C

Capacitance
Capacitance is the charge stored per unit voltage between conductors separated by a dielectric, measured in farads.
Practical capacitors often use microfarads, so a 10 µF value must be entered as 10×10−6 F.
Capacitive reactance
Capacitive reactance is a capacitor's opposition to sinusoidal current, measured in ohms and decreasing as frequency or capacitance rises.
A 10 µF capacitor has about 318 Ω reactance at 50 Hz and about 39.8 Ω at 400 Hz.
Capacitor bank
A capacitor bank is a group of capacitors arranged to supply a required capacitive reactive power to a circuit or installation.
An automatic bank switches steps as motor loading changes, helping avoid excess leading compensation at light load.
Choke
A choke is an inductor used to oppose unwanted changing currents, offering greater ideal reactance at higher frequencies.
A choke in a filter can oppose high-frequency interference while offering much less opposition to steady DC.
Current triangle
A current triangle combines perpendicular in-phase and net reactive current components to find the resultant supply-current magnitude.
In-phase current of 5 A and net reactive current of 5 A give about 7.07 A supply current, not 10 A.
Cycle
A cycle is one complete repetition of a waveform, including its positive and negative portions and return to the same starting phase.
On a sine-wave trace, successive upward zero crossings mark the ends of one complete cycle.

D

Delta connection
A delta connection joins three phase windings end to end in a loop, placing each winding directly between two line conductors.
A balanced delta load has line current equal to 3 times its winding current and has no star-point neutral.
Detuned bank
A detuned bank is a capacitor-bank arrangement with series reactors that helps prevent harmful resonance with supply harmonics.
Where drives draw distorted current, a plain capacitor bank can overheat unless resonance risk is properly addressed.
Dielectric
A dielectric is the insulating material between capacitor conductors that supports an electric field and affects the stored charge.
Fuel replacing air between an aircraft probe's conductors changes the dielectric and raises measured capacitance.
Displacement power factor
Displacement power factor is the cosine of the phase angle between the fundamental-frequency voltage and current components.
A drive may have a near-unity displacement factor while distorted current lowers its true power factor.

E

Efficiency
Efficiency is the ratio of useful output power to active input power, commonly expressed as a fraction or percentage.
A motor's power factor does not say how much of its active electrical input emerges as mechanical shaft power.
Electric field
An electric field is the field associated with electric charge and voltage in which a capacitor stores recoverable electrical energy.
An ideal capacitor returns stored field energy to the circuit instead of converting it into average active power.

F

Frequency
Frequency is the number of complete cycles occurring each second, measured in hertz and equal to the reciprocal of the period.
A 400 Hz aircraft supply repeats eight times as often as a 50 Hz supply, without implying a higher voltage.

H

Half-cycle average
The half-cycle average is the mean value over one positive sine-wave half cycle, equal to the average of its full-wave-rectified form.
A 325 V peak sine wave has a half-cycle average near 207 V, below its approximately 230 V rms value.

I

Impedance
Impedance describes a circuit's total opposition to sinusoidal current, combining resistance and reactance with their phase relationship.
A coil's rms voltage divided by rms current gives impedance magnitude, not winding resistance alone.
Impedance triangle
An impedance triangle is a right triangle linking series resistance, net reactance and impedance magnitude for a sinusoidal circuit.
For 30 Ω resistance and 40 Ω reactance, its hypotenuse is 50 Ω, not the arithmetic sum of 70 Ω.
In-phase current component
An in-phase current component is the part of a sinusoidal current aligned with the voltage, responsible for active power input.
A motor drawing 10 A at power factor 0.8 has an 8 A in-phase component to combine with a heater current.
In-phase quantities
In-phase quantities are same-frequency waves that reach matching cycle positions together, giving a phase difference of zero.
In a pure resistor, voltage and current cross zero together, so their instantaneous product never becomes negative.
Inductance
Inductance is the property of a circuit or coil by which a changing current induces a voltage that opposes that change, measured in henries.
Adding turns or using an iron core generally increases a coil's inductance and its reactance at a fixed frequency.
Inductive reactance
Inductive reactance is an inductor's opposition to sinusoidal current from self-induction, measured in ohms and increasing with frequency.
A 0.1 H ideal coil has about 31.4 Ω reactance at 50 Hz but about 251 Ω at 400 Hz.
Instantaneous value
An instantaneous value is the voltage or current at one particular moment in a cycle, including its sign relative to the chosen reference.
A sine wave's instantaneous voltage is zero at a zero crossing even though the supply's rms rating is nonzero.

K

Kilowatt-hour
A kilowatt-hour is an energy unit equal to one kilowatt of active power used for one hour, distinct from a power rating.
A constant 1 kW heater running for two hours uses 2 kWh, even though its power rating remains 1 kW.

L

Lagging quantity
A lagging quantity is the one of two same-frequency waves that reaches a matching point later, measured against the stated reference.
An ideal inductor's current is 90° behind its voltage, equivalent to 5 ms on a 50 Hz supply.
Leading quantity
A leading quantity is the one of two same-frequency waves that reaches a matching point in its cycle earlier than the other.
For an ideal capacitor, the current reaches its positive peak a quarter cycle before the voltage does.
Line current
Line current is the current flowing through a supply line conductor; its relationship to winding current depends on the load connection.
Line current equals phase current in star, but it is 3 times balanced delta phase current.
Line voltage
Line voltage is the voltage measured between two line conductors, distinct from the voltage across one winding in a star connection.
A 230/400 V network has nominal 400 V line voltage, while one line to neutral gives about 230 V.

M

Microfarad
A microfarad is one millionth of a farad, written µF, and is a common unit for motor and power-factor correction capacitors.
A 10 mF entry is 1000 times a 10 µF value, changing both the calculated reactance and the predicted current.

N

Net reactance
Net reactance is the signed reactive opposition remaining after inductive and capacitive contributions in a series circuit are combined.
Reactances of 100 Ω inductive and 70 Ω capacitive leave 30 Ω inductive, giving lagging current.
Neutral conductor
A neutral conductor connects to a source neutral point and can carry load current, including the uncanceled current of unbalanced phases.
A balanced sinusoidal three-phase load gives zero neutral current, while unequal phase loads leave a residual.
Neutral current
Neutral current is the resultant current in the neutral conductor after the phase-current contributions combine with their timing.
Three resistive line currents of 10 A, 8 A and 6 A leave about 3.46 A in the neutral, not 4 A.
Nominal voltage
Nominal voltage is the assigned reference voltage identifying a supply system, around which its actual operating voltage can vary.
A 230/400 V label names a system's usual phase and line values without guaranteeing exact readings at every moment.

O

Overcorrection
Overcorrection occurs when added capacitive reactive power exceeds the lagging demand being compensated, leaving a leading supply current.
Leaving a large fixed bank connected after motors stop can raise supply current again and increase voltage.

P

Parallel resonance
Parallel resonance is cancellation of inductive and capacitive reactive branch currents at the supply connection of a parallel circuit.
Equal ideal LC branch currents can cancel in the supply while each branch continues to carry current.
Peak value
The peak value is a waveform's greatest positive value measured from zero; a symmetrical waveform has an equal negative peak magnitude.
A 230 V rms sine wave reaches about 325 V peak, so its insulation experiences more than 230 V.
Peak-to-peak value
The peak-to-peak value is the difference between the highest and lowest instantaneous values, spanning both sides of the zero line.
For a sine wave symmetrical about zero, 325 V peak corresponds to approximately 650 V peak to peak.
Period
The period is the time taken for one complete waveform cycle, measured in seconds and represented by the symbol T.
A 50 Hz supply has a period of 0.020 s; two adjacent zero crossings are only half that time apart.
Phase current
Phase current is the current flowing through one source winding or load element, which may differ from the current in a line conductor.
A delta element taking 8.70 A contributes to a balanced line current of about 15.1 A at the supply.
Phase difference
A phase difference is the time displacement between same-frequency sinusoidal quantities expressed as an angle within a complete cycle.
A current peak occurring 1.67 ms after the voltage peak at 50 Hz represents a lag of about 30°.
Phase sequence
Phase sequence is the order in which the three phase voltages reach matching cycle positions, determining a motor's field direction.
Interchanging any two lines reverses the phase sequence and therefore the rotation of a three-phase motor.
Phase voltage
Phase voltage is the voltage across one source winding or one load element, determined by its connection to the supply.
A delta winding on a 400 V line supply receives 400 V; a balanced star winding receives about 231 V.
Phasor
A phasor is an arrow representing the magnitude and phase angle of a sinusoidal quantity relative to other quantities of the same frequency.
Current is a convenient reference arrow in a series circuit because it is shared by all components.
Pole pair
A pole pair is one north magnetic pole and one south magnetic pole; a generator's pole-pair count links rotational speed with electrical frequency.
A four-pole generator has two pole pairs and produces 50 Hz when its rotor turns at 1500 rpm.
Power analyzer
A power analyzer is an instrument that measures electrical power quantities from voltage and current, including their timing and waveform effects.
For a distorted load, use a suitable true-rms analyzer to measure watts, apparent power and true power factor.
Power factor
Power factor is the ratio of active power to apparent power, describing active input for the load's total rms current demand.
The same electrical kilowatts require more supply current at power factor 0.7 than at 1, for fixed voltage.
Power triangle
The power triangle is a right triangle relating active, reactive and apparent power for sinusoidal voltage and current.
An active input of 1840 W and reactive demand of 1380 var combine into 2300 VA apparent input.
Power-factor correction
Power-factor correction is a reduction in supply reactive demand, commonly made by connecting capacitors in parallel with inductive loads.
With a capacitor added in parallel, a motor keeps its own current at fixed voltage while the motor-capacitor combination takes less upstream current.
Protective earth
Protective earth is a protective conductor connection that provides a fault-current path and is not intended as the normal load-current return.
Green-and-yellow commonly identifies protective earth in European wiring, while green or bare copper serves US equipment ground.

R

Reactive current component
A reactive current component is the part of a sinusoidal current 90° from the voltage, associated with field-energy exchange.
A 10 A, 0.8-lagging motor has a 6 A reactive component, which a leading capacitor current can offset.
Reactive power
Reactive power describes the alternating exchange of energy with magnetic and electric fields, measured in volt-amperes reactive.
Inductive and capacitive reactive powers offset, although their currents can still cause heating in real supply wiring.
Resonant frequency
The resonant frequency is the frequency at which inductive and capacitive effects cancel in the specified circuit arrangement.
A series combination of 0.1 H and 10 µF resonates at about 159 Hz, above which it behaves inductively.
rms value
The rms value is the DC voltage or current that would cause the same average heating in the same resistor as the changing waveform.
The 230 V rating of a sinusoidal supply is its rms voltage, which can be used in resistor power calculations.
Rotating magnetic field
A rotating magnetic field is the moving stator field created by spatially arranged windings carrying phase-displaced three-phase currents.
The field in a four-pole motor rotates at 1500 rpm on 50 Hz and 1800 rpm on 60 Hz.

S

Self-induction
Self-induction is the production of an induced voltage in a circuit by a change in that circuit's own current and magnetic field.
A coil's induced voltage opposes rising or falling current, explaining why its AC current lags its voltage.
Series RC circuit
A series RC circuit places resistance and capacitance in one current path, producing a supply current that leads its voltage.
For 120 Ω resistance and 50 Ω capacitive reactance, total impedance is 130 Ω and current leads by about 22.6°.
Series resonance
Series resonance is the condition where inductive and capacitive reactance cancel, leaving resistance as the series impedance.
At a fixed supply voltage, a series RLC circuit reaches its greatest current when it reaches resonance.
Series RL circuit
A series RL circuit places resistance and inductance in one current path, producing a supply current that lags its voltage.
Increasing frequency raises inductive reactance and usually reduces current when resistance and supply voltage stay fixed.
Single-phase supply
A single-phase supply provides one alternating voltage to a load through two current-carrying conductors, which may be line and neutral or two lines.
A 240 V load connected between two split-phase hot conductors still operates from a single-phase source.
Slip
Slip is the difference between synchronous field speed and induction rotor speed, expressed as a fraction of synchronous speed.
A rotor at 1450 rpm under a 1500 rpm field has about 3.3% slip during normal motoring operation.
Split-phase supply
A split-phase supply is a single-phase source with a center-tapped winding, giving two equal hot-to-neutral voltages 180° apart.
A 120/240 V home supply gives 120 V from either end to neutral and 240 V between the two hot ends.
Star connection
A star connection joins one end of each phase winding at a common point, with each other end connected to a line conductor.
The common star point can provide a neutral, and each line carries the current of its connected phase winding.
Star-delta starting
Star-delta starting starts a motor in star and then changes to delta when it is rated to run in delta at the supply line voltage.
A 400/690 V Δ/Y motor can use this method on 400 V, while a 230/400 V Δ/Y motor must run in star there.
Synchronous speed
Synchronous speed is the rotational speed of an AC motor's magnetic field, set by supply frequency and the number of pole pairs.
Use ns=60f/p with two pole pairs, not four poles, when calculating a four-pole motor's field speed.

T

Third harmonic
A third harmonic is a waveform component at three times the fundamental frequency; phase-current third harmonics can reinforce in the neutral.
Equal rms currents from electronic loads do not guarantee a current-free neutral because their waveform distortion matters.
Three-phase supply
A three-phase supply provides three alternating phase voltages of equal frequency, normally equal in magnitude and separated by 120 electrical degrees.
At 50 Hz, successive phase peaks are spaced by about 6.67 ms, one third of the 20 ms period.
Traction inverter
A traction inverter converts battery DC into controlled multiphase AC for a vehicle's drive motor and can return generated energy during braking.
It sets motor supply frequency and voltage, unlike the on-board charger that converts grid AC into battery DC.
Transformer-rectifier unit
A transformer-rectifier unit changes an AC voltage and rectifies it into DC to supply equipment requiring direct current.
An aircraft TRU can provide 28 V DC equipment power from its AC electrical distribution system.
True-rms meter
A true-rms meter measures the heating-related value of a waveform without relying on a sine-wave-only average-to-rms conversion.
Distorted drive currents need a true-rms instrument whose frequency range and current limits suit the measurement.

V

Voltage magnification
Voltage magnification is the occurrence of a component voltage larger than the supply voltage in a reactive circuit.
An inductor can have 460 V across it on a 230 V supply because a capacitor supplies an opposing voltage contribution.
Voltage triangle
A voltage triangle is a right-triangle representation of resistive and net reactive voltage components and their resultant supply voltage.
Series drops of 138 V and 184 V at right angles combine into a 230 V supply, despite totaling 322 V arithmetically.

W

Winding resistance
Winding resistance is the electrical resistance of the wire in a coil, which causes active power loss and limits its steady DC current.
A 12 Ω ohmmeter reading describes the coil's resistance, not its much larger possible 50 Hz impedance.

About this lesson

By StudeliReport a mistake